Address assignment
Operating Manual PSS u2 ES 4DO R 8A
1004548-EN-03
| 12
5
Address assignment
The module occupies 1 Byte in the process image of outputs.
PIO
Meaning
State
Bit 0
Output data O0
N/O contact O0.13/O0.14
0: N/O contact is open
1: N/O contact closed
Bit 1
Output data O1
N/O contact O1.23/O1.24
Bit 2
Output data O2
N/O contact O2.33/O2.34
Bit 3
Output data O3
N/O contact O3.43/O3.44
Bit 4-7
None
Permanently "0"