Technical Details
Operating Manual PSS u2 ES 4DO R 8A
1004548-EN-03
| 24
Environmental data
Shock stress
In accordance with the standard
EN 60068-2-27
Acceleration
150 m/s²
Duration
11 ms
Airgap creepage
In accordance with the standard
EN 60664-1
Overvoltage category
III
In accordance with the standard
EN 61131-2
Overvoltage category
II
Pollution degree
2
Protection type
In accordance with the standard
EN 60529
Housing
IP20
Mounting area (e.g. control cabinet)
IP54
Potential isolation
Potential isolation between
Relay output and relay output
Type of potential isolation
Protective separation
Rated surge voltage
6000 V
Potential isolation between
Relay output and periphery supply
Type of potential isolation
Protective separation
Rated surge voltage
6000 V
Potential isolation between
Relay output and module supply
Type of potential isolation
Protective separation
Rated surge voltage
6000 V
Potential isolation between
Periphery supply and module supply
Type of potential isolation
Functional insulation
Rated surge voltage
2500 V
Mechanical data
Mechanical life
50,000,000 cycles
Material
Housing
PC
Mounting type
plug-in
Dimensions
Height
110,8 mm
Width
25 mm
Depth
75,3 mm