Technical details
Operating Manual PSSu E F 2DOR 8(-T)(-R)
21334-EN-13
| 34
Environmental data
312225
314225
315225
Climatic suitability
In accordance with the
standard
EN 60068-2-78
EN 60068-2-78
–
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
–
Condensation during op-
eration
Not permitted
Short-term (only with
separated extra low
voltage)
Short-term (only with
separated extra low
voltage)
Max. operating height
above sea level
2000 m
2000 m
2000 m
Max. operating height
above sea level in accord-
ance with EN 81-1, EN
81-2 and EN 115-1
2000 m
2000 m
–
EMC
EN 61000-4-2, EN
61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN
61000-4-6, EN 61000-6-2,
EN 61000-6-4
EN 61000-4-2, EN
61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN
61000-4-6, EN 61000-6-2,
EN 61000-6-4
EN 61000-4-2, EN
61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN
61000-4-6, EN 61000-6-2,
EN 61000-6-4
Vibration
In accordance with the
standard
EN 60068-2-6
EN 60068-2-6
EN 50125-3
Frequency
10 - 150 Hz
10 - 150 Hz
5 - 2000 Hz
Acceleration
1g
1g
0,23g
Broadband noise
In accordance with the
standard
–
EN 60068-2-64
EN 61373
Frequency
–
5 - 500 Hz
5 - 150 Hz
Acceleration
–
1,9grms
0,79 g RMS
Shock stress
In accordance with the
standard
EN 60068-2-27
EN 60068-2-27
EN 50125-3
Number of shocks
6
6
20
Acceleration
15g
15g
2g
Duration
11 ms
11 ms
11 ms
In accordance with the
standard
EN 60068-2-27
EN 60068-2-27
EN 61373
Number of shocks
1000
1000
20
Acceleration
10g
10g
5g
Duration
16 ms
16 ms
30 ms
Supply interruptions
In accordance with the
standard
–
–
EN 50155
Class
–
–
S2, C1, C2
Airgap creepage
In accordance with the
standard
EN 60664-1
EN 60664-1
EN 50124-1
Overvoltage category
III
III
OV2
Pollution degree
2
2
PD2