Technical details
Operating Manual PSSu E F 2DOR 8(-T)(-R)
21334-EN-13
| 37
Number of cycles x 1000
Switching current (A)
Fig.: Service life graph / Switching capability 60 VDC
Example
}
Inductive load: 0.2 A
}
Utilisation category: AC15
}
Contact service life: 1 000 000 cycles
Provided the application to be implemented requires fewer than 1 000 000 cycles, the PFH
value (see
Technical details [
31]
) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all relay con-
tacts. With capacitive loads, any power surges that occur must be noted. With DC contact-
ors, use flywheel diodes for spark suppression.
We recommend you use semiconductor outputs to switch 24 VDC loads.