][BA_Betrieb Störung LED "Err" Sys A + B
A module error is displayed via the "Err" LED (see section entitled "Dis-
play elements"), signalled to the head module and then entered in the
head module's
Error stack, with PSSu in system environment A
Diagnostic log, with PSSu in system environment B.
][BA_Betrieb Fehler FS Eingang
The module can detect the following errors:
Module error
Explanation
Remedy
Start-up error
Error as the PSSu system starts up
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry does
not match the actual hardware regis-
try.
FS communication error
Error during FS communication Change
faulty
module.
Bus termination error
There is no terminating plate or there is
a bad contact with the module bus.
Install a terminating plate with inte-
grated end bracket or insert the base
modules together correctly.
Temperature error: too warm
Ambient temperature too high:
Error stack entry/diagnostic log entry
Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.
Error in the feedback loop
FS input detects an error in the feed-
back loop or FS input is defective.
Check FS input, check the configura-
tion of the feedback loop, check the
signals, or check the wiring and con-
tacts.
Input error
Error during the cyclical input test.
Possible cause: Input defective.
Change faulty module.
Test pulse error
Possible causes: Short circuit be-
tween a test pulse and a supply volt-
age, or a defective module.
Rectify the short circuit or change the
faulty module.