Connecting the PSSu system
Installation Manual PSSuniversal
21262-EN-07
51
Disconnect cable:
}
Using the screwdriver, press the actuator button down as far as it will go [4], keep it
held down and pull the cable out of the plug connection [4].
[1]
[2]
[3]
[4]
8 mm
(0.315")
Fig.: Connect and disconnect the cables
6.6.1
Cable requirements
Please note:
}
The cable cross section with spring-loaded terminals without ferrules is 0.20 – 1 mm
2
,
22 -16 AWG.
}
If you are using multi-core or fine-core cables we recommend ferrules in accordance
with DIN 46228/Part 1 or DIN 46228/Part 4, 0.2 ... 1 mm
2
. To crimp the ferrules we re-
commend crimping pliers (crimp form A) conforming to EN 60947-1, such as the PZ 6/5
from Weidmüller, for example.
}
Terminal points per connection: 1
}
Stripping length: 8 mm
6.7
Wiring test and function test
CAUTION!
The PSSuniversal may be damaged by wiring errors or by modules being
inserted incorrectly.
For this reason, please follow the correct sequence when commissioning.
Prerequisite:
}
Mechanical structure is complete.
}
Wiring is finished.
}
Voltage is not yet applied.