background image

 

10

 

TROUBLESHOOTING

 

 

PROBLEM REMEDY 

1. System bypass open. 

Close bypass valve and open inlet/outlet valves 

2. Excessive air flow. 

Check rated output capacity of air compressor; a larger system 
may be needed. 

3. High inlet air temperature. 

A larger system or after-cooler may be needed (consult factory) 

4. Dirty heat exchanger. 

Disconnect dryer inlet/outlet and flush with steam cleaner and 
copper solvent. 

5. Drain malfunction. 

Clean or replace. 

6. Not draining all moisture. 

Adjust on/off times to drain – longer and/or more frequently. 

7. Refrigerant compressor cycling 
due to high refrigerant pressure or 
overload 

a. Overloaded unit. 

 

b. Dirty atmosphere. 

 

c.  High ambient temperature. 

 

d.  Condenser fan motor failure. 

 

e. Incorrect high-pressure 

shutdown setting. 

 

f. Bad compressor. 

 
 
 
Reduce load or install larger system. 

 

Clean condenser and install filter. Relocate unit or convert to 
water-cooled unit. 
Provide suitable ventilation or relocate unit. Consult factory. 

 

Repair or replace. 

 

Correct to: R-134a: 235 PSIG/16.2 BarG 
                  R-22:     350 PSIG/2724.1 BarG  

 

Replace compressor and liquid and suction line filters. 

8. Refrigerant compressor cycling on 
low pressure 

a. Refrigerant low. 

 

b.  Incorrect low pressure control 

setting. 

 
 
 

c. Low-pressure control 

malfunction. 

 
 
Inspect for leaks, repair, evacuate and recharge. Consult factory. 

 

Correct to: 
R-134a: cut out 20 PSIG/1.38 BarG, cut in 30 PSIG/2.07 BarG 
R-22:    cut out 40 PSIG/2.16 BarG, cut in 60 PSIG/4.14 BarG 
Units supplied with pump down: 
R-22:    cut out 25 PSIG/1.73 BarG, cut in 35 PSIG/2.42 BarG 

 

Replace. 

9. Refrigerant suction temperature 
too low/freeze up. 

a.  Check fan cycle switch (if 

supplied). 

 

 
 
 

b.  Ambient temperature too low. 

Correct settings: 
#1 Fan 
R-134a: cut out 75 PSIG/5.2 BarG, cut in 125 PSIG/8.6 BarG 
R-22   : cut out 150 PSIG/10.4 BarG, cut in 230 PSIG/15.9 BarG 

 

#2 Fan 
R-134a: cut out 110 PSIG/7.6 BarG, cut in 160 PSIG/11.4 BarG 
R-22   : cut out 200 PSIG/13.8 BarG, cut in 275 PSIG/19 BarG 
Relocate unit to a heated room/install low ambient package. 
Consult factory. 

Summary of Contents for ADR Series

Page 1: ...Air Dryer R and ADR Series Pioneer Air Systems Inc 210 Flatfork Road Wartburg TN 37887 Tel 800 264 1AIR 423 346 6693 Fax 423 346 3865 423 346 7522 Email sales pioneerair com Internet Address http www pioneerair com ...

Page 2: ...Micro Monitor Control 8 Micro Monitor Diagram 8 Maintenance 8 Automatic Drain 8 10 Year Limited Warranty 8 Troubleshooting 10 Warranty Extension Form 11 Mechanical Layout Electrical Wiring Diagram Recommended Spare Parts List Maximum Working Pressure Dryer Size 170 PSIG 11 7 BarG R3000 and up ADR1500 and up 200 PSIG 13 8 BarG R235 to R2500 ADR250 to ADR1250 250 PSIG 17 2 BarG R10 to R200 ADR15 to ...

Page 3: ...ned for installation in a protected area that is clean dry and has and ambient temperature range of 50 to 100o F 10 to 37o C For installation in other temperatures consult factory Consider heat rejection when locating the unit Position the unit to permit free circulation of cooling air for the condenser See Table 1 for safe distance placement Table 1 Recommended Safe Distance from Wall Model Intak...

Page 4: ...sludge rust and free moisture In a newly installed piping system the prefilter element may need to be changed within a few days of installation to remove weld sludge rust and etc After all power and connections have been made the unit is ready for operation Generally dryers are shipped with a charge of refrigerant with all refrigeration service ports closed Switch the main disconnect on allowing t...

Page 5: ...led to the 35o F 2o C range in the air refrigerant heat exchanger Cooling the compressed air causes condensation of moisture which is separated by a highly efficient moisture separator An automatic drain periodically drains the condensate Cold dry air from the separator flows through the air air heat exchanger where it is reheated by the incoming warm air Reheating increases the volume of air pre ...

Page 6: ...protect the refrigerant system from foreign particles To provide relatively constant temperature in the air refrigerant heat exchanger R75 or ADR40 and larger the refrigeration system is also equipped with a hot gas bypass valve Theses mix hot and cold refrigerant to give a stable suction pressure and temperature Thus near constant dew point is maintained at fluctuating load conditions Mr Goodaire...

Page 7: ...7 INSERT FLOW DIAGRAM ...

Page 8: ...year prorated compressor warranty apply on standard Pioneer products Pioneer standard dryers are warranted to be free from defects in material and workmanship for a period of one year from the date of shipment 15 months for distributor stock units provided the equipment is used according to the company s recommended usage Liability is limited to the repair refund or replacement in kind at the comp...

Page 9: ...contact factory allowing it to cycle on high pressure will burn up the compressor motor Because of higher pressure and electrical voltage only qualified service personnel should work on the equipment For critical applications the factory recommends that the customer install a back up system WARNING Remove air pressure from the device under pressure before working on it ...

Page 10: ...ide suitable ventilation or relocate unit Consult factory Repair or replace Correct to R 134a 235 PSIG 16 2 BarG R 22 350 PSIG 2724 1 BarG Replace compressor and liquid and suction line filters 8 Refrigerant compressor cycling on low pressure a Refrigerant low b Incorrect low pressure control setting c Low pressure control malfunction Inspect for leaks repair evacuate and recharge Consult factory ...

Page 11: ...0 mile Travel food and lodging costs are the responsibility of the customer and are invoiced on a cost basis Name ___________________ Title ______________________ Company Name _______________________________________ Address _____________________________________________ City St Zip __________________________________________ Complete and return a copy to Phone __________________ Model ______________...

Reviews: