- 32 -
GB
Parameter Description
Default
min
MAX
P23
Polarity for safety device alarm
0
0
1
0: DI Open = HP Alarm active
1: DI closed = HP Alarm active
P24
P25
Duration of Sterilization process
15 min
0 min
90 min
P26
Minimum temperature for sterilization start
+15°C
0°C
100°C
P27
Min. temperature for the core probe heating start
-5°C
-50°C
+50°C
P28
Duration of the core probe heating
90 sec
0 sec
600 sec
P29
Final temperature of core probe heating
+30°C
0°C
100°C
P30
Differential for ON-OFF compressor
+1°C
0°C
20°C
P31
Min.time between OFF-ON compressor
2 min
0 min
30 min
P32
Offset for core probe with faulty cold room probe and core probe not inserted
-2°C
-10°C
10°C
P33
Min. core probe temperature for chilling/freezing start
+70°C
0°C
90°C
P34
Duration of core probe insertion test (0=text excluded)
5 min
0 min
240 min
P35
Fan ON with compressor OFF in conservation phase
30 sec
0 sec
999 sec
P36
Fan OFF with compressor OFF in conservation phase
300 sec
0 sec
999 sec
P37
Core temperature difference during core probe insertion test
+4°C
0
+10°C
P38
Temperature difference between core and cold room during
+5°C
0
+10°C
core probe insertion test
P39
P40
Unit address for external haccp monitoring system
1
1
147
P41
Serial connection: 0 = not used
1
0
2
1 = Printer
2 = ModBus
P42
BaudRate: 0= 2400; 1 = 4800; 2 = 9600;
2
0
2
P43
Parity : 0= no parity; 1= odd; 2 = even
2
0
2
P44
Time interval between 2 following prints
10 min
1 min
60 min
P50
Carrying out defrosting at chilling/freezing cycle:
0
0
1
0=No;1=Yes
P51
Final temperature at the end of the defrosting process
+8°C
-10°C
+30°C
P52
Max. duration of the defrosting process
15 min
1 min
90 min
P53
Time interval between 2 following defrosting process in conservation phase:
0=excluded
0 hours
0
18 hours
P54
Defrosting type:
0
0
2
0= wit hair circulation 1= hot-gas 2= electric
P55
Dripping time after defrosting process
1 min
0 min
90 min
P56
Delay for compressor activation with hot-gas defrosting
0 sec
0 sec
600 sec
P57
Minimum temperature for defrosting process activation
+3°C
-10°C
+30°C
P58
Temperature differential for fan stop after defrosting
+5°C
0°C
+10°C
P60
Compressor ON in chilling cycle with faulty cold room probe and core probe inserted
3 min
0 min
60 min
P61
Compressor OFF in chilling cycle with faulty cold room probe and core probe inserted
7 min
0 min
60 min
P62
Compressor ON in freezing cycle with faulty cold room probe and core probe inserted
8 min
0 min
60 min
P63
Compressor OFF in freezing cycle with faulty cold room probe and core probe inserted
2 min
0 min
60 min
P65
Delay for compressor start-up after swichting on electronic board
2 min
0 min
60 min