AM2020/AFP1010 Troubleshooting Guide  50432  Revision A  8/13/97

23

The "DEL" function can be used in the Control-By-Event equation of an output
type device (CMX, XPC, or XPR modules) or of a reverse-activated zone to delay
the activation of that output device or zone and as an option turn the output
device or zone off after a specified time.

Equation Format:

DEL(dd.dd.dd tt.tt.tt (Zn))

Example 1: Assume that Zone 205 is a reverse activated zone with the following Control-
By-Event equation:

DEL(00.01.00 (Z12))

This means that after Zone 12 has been activated for one minute, Zone 205 will activate
and stay active until either the panel is reset or Zone 12 returns to normal.

Example 2: Assume that Zone 206 is a reverse activated zone with the following Control-
By-Event equation:

DEL(00.01.00 00.05.00 (Z12))

This equation means that after Zone 12 has been activated for one minute, Zone 206 will
activate and stay active for five minutes unless the panel is reset or Zone 12 returns to
normal.

The operand in a "DEL" equation (Zone 12 in both the above examples) may be
either an input device, a forward activated zone or a reverse activated zone.

Application Note: The "DEL" equation may be used to delay the activation of the main
sounders in a building to allow time for the source of the alarm to be investigated.  Note:
This application should only be used after obtaining written permission from the Local
Authority Having Jurisdiction.  Consider the following for a hypothetical building:

All the smoke detectors in the building are mapped to Zone 1 (an FZON).
All the pull stations in the building are mapped to Zone 200 (an RZON).
The control modules that control the main sounders in the building are also mapped to
Zone 200.

Zone 200 is given the following CBE:

DEL(00.01.00 (Z1))

Note: All the smoke detectors that are mapped to Zone 1 should be programmed as non-
tracking to avoid resetting the one minute delay timer.

When a smoke detector goes into alarm it activates Zone 1.  A counter is started
that will delay the activation of Zone 200 for one minute, thus delaying the main
sounders in the building and allowing the security guard time to investigate the
source of the alarm.

A control module (mapped to Zone 1) may be configured to sound a local
sounder at the security guard's location to alert the guard to the possible fire in
the building.  In addition, the panel's piezo sounder will automatically activate.

Once Zone 1 is activated, three possible scenarios may occur:

1) The guard goes to investigate the alarm and discovers that it was a false

activation.  In which case he can reset the panel before the building is
needlessly evacuated.

2) The guard goes to investigate the alarm and realizes that it is indeed a fire.

So he pulls the closest manual pull station which causes an immediate

dd.dd.dd is the time delay in
an hour.minutes.seconds
format.

 Zn is the input device or zone that
acts as a trigger for the delay timer to
start.

tt.tt.tt is the time that the output device or zone will stay
on after activation (this is optional, leaving it out will
result in the output device or zone staying on until the
operand  restores or until the panel is reset).

How Does the "DEL"
Function Work?

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for Notifier AFP1010

Page 1: ...AFP1010 Troubleshooting Guide DOCUMENT NUMBER 50432 8 13 97 REVISION A 50432 A ECN 97 333 12 Clintonville Road Northford CT 06472 Phone 203 484 7161 Fax 203 484 7118 www PDF Zoo com firealarmresource...

Page 2: ...oper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instru...

Page 3: ...ystem Will Not Accept Any New Programming Information 17 The System Loses all Programmed Information 17 The Operator Gets Kicked out of Programming Every Time a New Point is Added 18 The Piezo Sounder...

Page 4: ...power from the panel 4 Allow the panel to discharge for approximately one minute before connect ing or disconnecting any ribbon cables or harnesses or removing or adding any circuit boards When reapp...

Page 5: ...this circuit is shown below Point a on the schematic represents the electrical location of the cabinet which is at earth ground potential During a normal condition the pulse detection circuitry detec...

Page 6: ...It is important to realize that these paths to ground need not be dead shorts In the very common case shown below multiple seemingly minor ground faults combine to exceed the ground fault threshold of...

Page 7: ...will fall below the ground fault circuit threshold and a ground fault indication will result When using shielded cable for the SLC loop wiring it is important to realize that since a conductor the SL...

Page 8: ...it goes below 50 000 ohms a ground fault will result That means that 12 73 microfarads is the maximum allowable amount of capacitance collectively on all loops leaving the panel Figure 2 7 Schematic r...

Page 9: ...t condition 5 Disconnect all field wiring from terminal block TB3 on the MPS 24A 6 Power down the panel Disconnect the ribbon cable that connects the SIB plug P4 to the DIA plug P4 Disconnect the ribb...

Page 10: ...tion replace the faulty ICA 4 ICA 4L chassis and return the LIBs to their original positions For more information on LIB corrective action refer to Section Five Trouble Code T18 Drift Compensation Err...

Page 11: ...munications Invalid Reply clears Corrective Action If power has not been removed from the system recently and a Drift Compen sation error is present follow the procedure below 1 Remove the detector in...

Page 12: ...tripped 4 Reapply power to the system and measure pin 1 and pin 7 of P2 or P4 again with the harnesses disconnected If 24 VDC is not present the main power supply must be replaced If 24 VDC is presen...

Page 13: ...a short circuit in the wiring of either a Control Module or an XPC point Corrective Action 1 Check field wiring 2 Check the style of the field wiring Style Y or Z 3 Remove field wiring and place ELR...

Page 14: ...10L is an older pull station which is no longer available it should be programmed as a PULL The BGX 101L the most common pull station must be programmed as an MPUL 4 Once the programming has been veri...

Page 15: ...e pro grammed with an FORC CMXC or other similar type I D 4 Confirm that each address point on each of the expander cards is pro grammed appropriately If performing Canadian Dual Stage with XPC cards...

Page 16: ...on The MPS TR is designed to supervise any of the MPS series power supplies when they are remotely mounted Yes Presently there is only one way to reset the AM2020 AFP1010 from a keyswitch either remot...

Page 17: ...ould come from remotely powered annunciators If an annunciator is powered from a remote source this source of power may back feed into the control panel through the EIA 485 connection on the Serial In...

Page 18: ...ll Point Programming 4 Do not acknowledge this trouble 5 Instead immediately reenter Full Point Programming and begin to program the next point As soon as the user reenters Full Point Programming the...

Page 19: ...er number FZON In addition once activated an FZON will execute it s Control By Event CBE list which can only consist of a number of things to activate Example Let s assume that Zone 10 and Zone 11 are...

Page 20: ...above examples a reverse activated zone Zone 208 may reference another RZON Zone 201 in it s equations provided that the zone that it is referencing is numerically lower The OR function may reference...

Page 21: ...ivalent of a three input AND equation The above equation can also be visualized in electrical terms as three normally open switches in series Figure 3 7 Electrical equivalent of a three input AND equa...

Page 22: ...NE Zn Example 1 Assume that Zone 220 is a reverse activated zone with the following Control By Event equation XZONE Z48 This means that when any two or more initiating devices detectors monitor module...

Page 23: ...ilding are mapped to Zone 1 an FZON All the pull stations in the building are mapped to Zone 200 an RZON The control modules that control the main sounders in the building are also mapped to Zone 200...

Page 24: ...at Zone 236 will be activated everyday of the week excluding Saturdays and Sundays from 8 00 AM until 5 00 PM Example of Equation Type 2 Assume that Zone 225 is a reverse activated zone with the follo...

Page 25: ...ped to Zone 200 Zone 200 is given the following CBE SDEL 00 01 00 Z1 When a smoke detector goes into alarm it activates Zone 1 A counter is started that will delay the activation of Zone 200 for one m...

Page 26: ...Sensitivity in either Full or Partial System Program ming 2 Assign Zone 240 reverse activated as the High Day Night zone 3 Set the sensitivity of all the addressable detectors to MEDIUM in Full or Pa...

Page 27: ...alarm points to latching operation Selected Listing NFPA Standard Default Module Programming 72A NFPA 72 1993 Local Fire Alarm Systems L1M96 EVGA Type ID Must be used to activate Notification Applianc...

Page 28: ...ng the CRT to the panel and connecting it to the SIB with a short length of cable If it still does not function replace the CRT The AM2020 AFP1010 is not receiving the proper handshaking signal from t...

Page 29: ...s not correct noise problems Further troubleshooting is recommended check wiring and or call Notifier Technical Services for more information No In Full or Partial Point Programming the control panel...

Page 30: ...allel We recommend that during program ming the LCD 80 should be disconnected to avoid unwanted interference from terminal supervision messages sent from the LCD 80 to the fire alarm control panel How...

Page 31: ...20 AFP1010 batteries first and then AC Reapply power AC first then batteries 2 If the trouble does not clear call Notifier Technical Support During the normal CPU polling response cycle which is expla...

Page 32: ...power from the AM2020 AFP1010 batteries first and then AC Reapply power AC first then batteries 2 If the trouble does not clear call Notifier Technical Support SCB stands for Serial Communication Bus...

Page 33: ...is specific trouble will be generated if the AVPS 24 is not programmed into the system and the trouble cable is connected to the CPU Corrective Action 1 Program the AVPS 24 into the system using eithe...

Page 34: ...Section 2 AM2020 AFP1010 Hard ware This trouble will occur if the standby batteries have been disconnected This trouble will also be generated if the batteries have become severely over or under charg...

Page 35: ...nstalled in the ICA 4L chassis but has not been programmed in Full or Partial System Programming Second if the LIB has been programmed but has not been physically installed This trouble will also occu...

Page 36: ...ation that one of the SLC loop drivers on the LIB board has failed Corrective Action 1 Confirm that the loop wiring matches the LIB programming 2 Remove the field wiring from the LIB in case there is...

Page 37: ...then AC Wait one minute Reapply power AC first then batteries 2 If the trouble does not clear call Notifier Technical Support Trouble Codes T2C T3C T4C etc apply to Loop Interface Boards 1 through 10...

Page 38: ...ming 5 Replace the CRT Corrective Action for LCD 80 inTerminal Mode 1 Check 485 wiring 2 Check that SW3 1 and 2 are set properly for all LCD 80s that exist 3 If you have both LCD 80 and CRT is the CCM...

Page 39: ...tifier Technical Support Each time the system is powered up or reset the DIB performs a test of the operating system EPROM on the DIB board by looking at the checksum This trouble is generated if the...

Page 40: ...n error condition on the printer Corrective Action 1 Verify that the printer is on line 2 Verify that the printer has paper and it is not jammed 3 Make sure the EIA 232 is plugged into the correct por...

Page 41: ...ed if the CPU has tried to send the same message to the ISIB several times and each time the message was received it was invalid Corrective Action 1 Remove power from the AM2020 AFP1010 batteries firs...

Page 42: ...nfiguration MIB thresholds node address and port configura tion 4 Cycle power 5 If the trouble does not clear call Notifier Technical Support A NFN communications fault has been detected on the indica...

Page 43: ...FN configuration MIB thresholds node address and port configura tion 4 Cycle power 5 If the trouble does not clear call Notifier Technical Support An undefined trouble has occurred in the system Corre...

Page 44: ...rophone on the AMG for 20 seconds 2 Check if the AMG microphone is unplugged 3 Check if the FFT 7 wiring is correct 4 Check if the SCS has correct programming of its switch groups 5 Check if the UDACT...

Page 45: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 45 NOTES www PDF Zoo com firealarmresources com...

Page 46: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 46 NOTES www PDF Zoo com firealarmresources com...

Page 47: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 47 NOTES www PDF Zoo com firealarmresources com...

Page 48: ...s NO NO NO NO NOTIFIER TIFIER TIFIER TIFIER TIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for whi...

Reviews: