AM2020/AFP1010 Troubleshooting Guide 50432 Revision A 8/13/97
41
Corrective Action:
1) Check the status of the printer.
This trouble is produced when the panel is in Walk Test mode. It is a reminder
that all of the LIB boards that are participating in Walk Test are incapable of
generating an alarm. All other LIBs will still function.
Corrective Action:
1) Exit Walk Test to restore complete fire protection.
This trouble is produced when the modem feature is enabled in either Full or
Partial System Programming. It is intended to be a reminder that the entire
system must be retested after the remote programming has been completed.
Corrective Action:
1) Complete remote programming.
2) Disable the modem feature in Full or Partial System Programming.
3) Retest the system.
Each time the system is powered up, the DIA performs a test of the nonvolatile
RAM chip. This test checks the write capability of the chip. If a problem is
detected writing to the chip, this trouble will be generated.
Corrective Action:
1) Contact Notifier Technical Support for a replacement nonvolatile RAM chip.
This trouble message will be generated if the CPU has tried to send the same
message to the ISIB several times and each time the message was received it
was invalid.
Corrective Action:
1) Remove power from the AM2020/AFP1010, batteries first and then AC. Wait
one minute. Reapply power - AC first, then batteries.
2) If the trouble does not clear, call Notifier Technical Support.
During the normal ISIB polling/response cycle, this trouble will be generated if
the response received by the ISIB is invalid or corrupt.
Corrective Action:
1) Remove power from the AM2020/AFP1010, batteries first and then AC. Wait
one minute. Reapply power - AC first, then batteries.
2) If the trouble does not clear, call Notifier Technical Support.
The microprocessor on the ISIB has a number of tasks that it must continually
accomplish. The executive routine keeps track of these tasks and sequentially
sends them to the microprocessor. The "micro" is given a certain amount of time
to accomplish each task. If it does not finish the current task in the allotted time,
this trouble is generated.
TD6 Fire Protection is
Limited During Walk Test.
TD7 Remote Program-
ming Mode Activated.
Retest System.
TD8 Catastrophic DIA
Nonvolatile RAM Failure.
TF0 ISIB SCB Receive
Failure.
TF1 ISIB Data Message
Received Error.
TF2 ISIB Executive
Routine Re-entered.