Intelligent Plug-In Model 5251RP

Rate-of-Rise Temperature Sensor

with Fixed Temperature Alarm

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before installing sensors, refer to NFPA 72, and 101 (Life Safety Code)  for  information on sensor spacing, placement, zon-
ing, and special applications.

GENERAL DESCRIPTION

Model 5251RP is an intelligent sensor that utilizes a state-of-the-art thermistor sensing circuit for fast response. This sen-
sor is designed to provide open area protection with 50 foot spacing capability and is intended  for use with compatible
control panels only.

Two LEDs on each sensor light to provide 360

°

 visibility of the sensor indication. The LEDs can be latched ON by code

command from the panel for an alarm indication. The LEDs can also be unlatched to the normal condition by code com-
mand. Remote LED annunciator capability is available as an optional accessory (Part No. RA400Z).

SPECIFICATIONS

Diameter:

6.1 inches (155 mm) installed in B210LP
4.1 inches (104 mm) installed in B501

Height:

2.0 inches (51 mm)

Weight:

5 ounces (150 gm)

Installation Temperatures:

-4

°

F to 100

°

F (-20

°

C to 38

°

C)

Operating Humidity Range:

10% to 93% Relative Humidity Non-condensing

Mounting:

B210LP flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit

Voltage Range:

15 to 28 Volts DC Peak

Standby Current:

300 

µ

A @ 24 VDC (one communication every 5 seconds with LED blink enabled)

LED Current:

6.5 mA @ 24 VDC

Fixed Temperature Rating:

135

°

F (57

°

C)

Rate-of-Rise Detection:

Responds to greater than 15

°

F/min.

WIRING GUIDE

Refer to the installation instructions for the particular plug-in base being used: 1) for the B210LP base (D250-01-00); 2) for
the B501 base (D550-02-00); 3) for the RMK400 used with the B501 base (D450-07-00). Bases are provided with screw ter-
minals for power, ground, and remote annunciator connections. See Figure 1.

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for System Sensor 5251RP

Page 1: ... the normal condition by code com mand Remote LED annunciator capability is available as an optional accessory Part No RA400Z SPECIFICATIONS Diameter 6 1 inches 155 mm installed in B210LP 4 1 inches 104 mm installed in B501 Height 2 0 inches 51 mm Weight 5 ounces 150 gm Installation Temperatures 4 F to 100 F 20 C to 38 C Operating Humidity Range 10 to 93 Relative Humidity Non condensing Mounting B...

Page 2: ...cating alarm and annunciating the panel 3 Reset the detector at the system control panel B Test sensitivity from the control panel C Direct Heat Method Hair dryer of 1000 1500 watts 1 From the side of the detector direct the heat toward the sensor Hold the heat source about 6 inches 15cm away to prevent damage to the cover during testing NOTE All wiring must conform to applicable local codes ordin...

Page 3: ...gure 3 Figure 2 Views showing position of test magnet MAINTENANCE NOTE Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temporarily be out of service Disable the loop or system undergoing maintenance to prevent unwanted alarms It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors...

Page 4: ...ed through the local manufacturer s representative Though heat detectors are designed for long life they may fail at any time Any heat detector fire system or any component of that system which fails shall be repaired or replaced immediately Refer to NFPA 72 for application This heat detector is designed to activate and initiate emergency action but will do so only when it is used in conjunction w...

Reviews: