2. The LEDs on the detector should light when the temperature at the detector reaches 135

°

F  (57

°

C). If the LEDs fail

to light, check the power to the detector and the wiring in the detector base.

3. Reset the detector at the system control panel.

Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested. If the detectors still fail
these tests they should be returned for repair.

Figure 3

Figure 2. Views showing position of test magnet.

MAINTENANCE

NOTE: Before cleaning notify the proper authorities that the system is undergoing maintenance, and therefore the system

will temporarily be out of service. Disable the loop or system undergoing maintenance to prevent unwanted
alarms.

It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors be cleaned at
least once a year. Use a vacuum cleaner to remove dust from the sensing chamber. See Figure 3.

TEST

MAGNET

LED

LED

PAINTED

SURFACE

TEST

MAGNET

PAINTED
SURFACE

MAGNET TEST MARKER

A78-1478-05

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for System Sensor 5251RP

Page 1: ... the normal condition by code com mand Remote LED annunciator capability is available as an optional accessory Part No RA400Z SPECIFICATIONS Diameter 6 1 inches 155 mm installed in B210LP 4 1 inches 104 mm installed in B501 Height 2 0 inches 51 mm Weight 5 ounces 150 gm Installation Temperatures 4 F to 100 F 20 C to 38 C Operating Humidity Range 10 to 93 Relative Humidity Non condensing Mounting B...

Page 2: ...cating alarm and annunciating the panel 3 Reset the detector at the system control panel B Test sensitivity from the control panel C Direct Heat Method Hair dryer of 1000 1500 watts 1 From the side of the detector direct the heat toward the sensor Hold the heat source about 6 inches 15cm away to prevent damage to the cover during testing NOTE All wiring must conform to applicable local codes ordin...

Page 3: ...gure 3 Figure 2 Views showing position of test magnet MAINTENANCE NOTE Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temporarily be out of service Disable the loop or system undergoing maintenance to prevent unwanted alarms It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors...

Page 4: ...ed through the local manufacturer s representative Though heat detectors are designed for long life they may fail at any time Any heat detector fire system or any component of that system which fails shall be repaired or replaced immediately Refer to NFPA 72 for application This heat detector is designed to activate and initiate emergency action but will do so only when it is used in conjunction w...

Reviews: