6/12

be laid separately from the power cables.
- Always connect the protection fuse (or equivalent device) in series with the power 
supply for each device.
- Always connect the protection fuse (or equivalent device) in series to the safety 
electrical contacts.
- During and after the installation do not pull the electrical cables connected to the 
device. If excessive tension is applied to the cables, the device may be damaged.

7.5 Additional prescriptions for safety applications with operator protection 
functions

Provided that all previous requirements for the devices are fulfilled, for installations 
with operator protection function additional requirements must be observed.
- The utilization implies knowledge of and compliance with following standards: 
EN ISO 13849-1, EN 62061, EN 60204-1, EN ISO 12100. 
- In the risk analysis, take into account that in manual start mode a possible sticking of 
the start button can lead to an immediate activation of the module.
- If expansion modules or external contactors are used, make sure that they have 
forcibly guided contacts and connect in feedback an NC contact of each device. 

7.6 Limits of use

- Use the device following the instructions, complying with its operation limits and the 
standards in force.
- The devices have specific application limits (min. and max. ambient temperature, 
maximum currents, IP protection degree, etc.) These limitations are met by the device 
only if considered individually and not as combined with each other. 
- According to EU directives, this device is not intended for private use.
- The manufacturer’s liability is to be excluded in the following cases:
1) Use not conforming to the intended purpose.
2) Failure to adhere to these instructions or regulations in force.
3) Fitting operations not carried out by qualified and authorized personnel.
4) Omission of functional tests.
- For the cases listed below, before proceeding with the installation contact our as-
sistance service (see paragraph SUPPORT):
a) In nuclear power stations, trains, airplanes, cars, incinerators, medical devices or 
any application where the safety of two or more persons depend on the correct opera-
tion of the device.
b) Applications not contemplated in this instruction manual.

 8 MARKINGS

The outside of the device is provided with external marking positioned in a visible 
place. Marking includes:
- Producer trademark
- Product code
- Batch number and date of manufacture. Example: CS1-123456 (A19). The last part 
of the production batch refers to the month of manufacture (A = January, B = February, 
etc.) as well as the year of manufacture (19 = 2019, 20 = 2020, etc.).

 9 TECHNICAL DATA

9.1 Housing

Material: Polyamide PA 66, self-extinguishing V0 acc. to UL 94
Protection degree: 

IP40 (housing), IP20 (terminal strip)

Cable cross section: 

0.2 … 2.5 mm

 (24 … 12 AWG)

Terminal tightening torque: 

0.5 … 0.6 Nm

9.2 General data

SIL (SIL CL): 

Up to SIL CL 3 acc. to EN 62061

Performance Level (PL):  

Up to PL e acc. to EN ISO 13849-1

Safety category: 

Up to cat. 4 acc. to EN ISO 13849-1

MTTF

D

:  

227 years

DC:  

High

PFH

D

1.18 E-10

Mission time: 

20 years

Ambient temperature: 

-25°C … +55°C

Storage temperature: 

-25°C … +70°C

Mechanical endurance: 

> 10 million operating cycles

Electrical endurance: 

> 100,000 operating cycles

Pollution degree: 

external 3, internal 2

Impulse withstand voltage U

imp

4 kV

Rated insulation voltage U

i

250 V

Overvoltage category: 

II

Air and surface distances: 

acc. to EN 60947-1

9.3 Power supply

Rated supply voltage U

n

:  

24 Vac/dc; 50…60 Hz 

(articles CS AR-01•

024)

 

120 Vac; 50…60 Hz 

(articles CS AR-01•

120)

 

230 Vac; 50…60 Hz 

(articles CS AR-01•

230)

 

10 … 30 Vdc

 (articles CS AR-01•

E02) 

Supply voltage tolerance:  

±15% of U

n

 

±10% of U

(articles CS AR-01•

E02)

Max. DC residual ripple in DC: 

10%

Power consumption AC: 

< 5 VA

Power consumption DC: 

< 2 W, < 3 W 

(articles CS AR-01•

E02)

9.4 Control circuit

Protection against short circuits: 

PTC resistance, Ih = 0.5 A

PTC times: 

Response time > 100 ms, release time > 3 s

Maximum resistance per input:  

 50 

Current per input: 

< 40 mA

Min. duration of start impulse t

MIN

> 100 ms, > 50 ms 

(articles CS AR-01•

E02)

Response time t

A

< 150 ms

Release time t

R1

< 15 ms

Release time  
in absence of power supply t

R

:  

< 70 ms, < 100 ms 

(articles CS AR-01•

E02)

 

Simultaneity time t

C

: unlimited

9.5 Output circuit

Output contacts: 

2 NO safety contacts

 

1 NC auxiliary contact

Contact type: 

forcibly guided

Material of the contacts: 

gold-plated silver alloy

Maximum switching voltage: 

230/240 Vac; 300 Vdc

Max. current per contact: 

6 A

Conventional free air thermal current I

th

:  6 A

Max. total current 

Σ

 I

th

2

72 A

2

Minimum current: 

10 mA

Contact resistance: 

 100 m

External protection fuse: 

4 A

Maximum switching load: 

1380 VA/W

Utilization categories acc. to EN 60947-5-1: 

AC15 (50 … 60 Hz)  

U

= 230 V, I

= 3 A 

DC13 (6 op. cycles/minute)  

U

= 24 V, I

= 4 A

Utilization category acc. to UL 508: 

C300

9.6 Compliance with standards

EN 60204-1, EN ISO 13855, EN ISO 14118, EN ISO 12100, EN ISO 13850, EN 60529, 
EN 61000-6-2, EN 61000-6-3, EN 61326-1, EN 60664-1, EN 60947-1, EN IEC 63000, 
EN ISO 13849-1, EN ISO 13849-2, EN 62061, UL 508, CSA C22.2 n° 14-95, 
GB/T14048.5-2017

9.7 Compliance with directives

Machinery Directive 2006/42/EC, EMC Directive 2014/30/EU, RoHS Directive 
2011/65/EU.

 10 SPECIAL VERSIONS ON REQUEST

Special versions of the device are available on request.
These special versions may differ substantially from the indications in these operating 
instructions.
The installer must ensure that he has received written information regarding the use 
of the special version requested (see paragraph SUPPORT).

 11 DISPOSAL

At the end of service life product must be disposed of properly, according to the 
rules in force in the country in which the disposal takes place.

 12 SUPPORT

The device can be used for safeguarding people’s physical safety, therefore in case of 
any doubt concerning installation or operation methods, always contact our technical 
support service:
Pizzato Elettrica Srl
Via Torino, 1 - 36063 Marostica (VI) - ITALY
Tel39.0424.470.930 
E-mail tech@pizzato.com
www.pizzato.com
Our support service provides assistance in Italian and English.

 13 EC CONFORMITY DECLARATION

I, the undersigned, as a representative of the following manufacturer:
Pizzato Elettrica Srl - Via Torino, 1 - 36063 Marostica (VI) – ITALY 
hereby declare that the product is in conformity with whatever prescribed by the 
2006/42/EC Machine Directive. The complete version of the present conformity 
declaration is available on our website www.pizzato.com
Marco Pizzato

DISCLAIMER:
Subject to modifications without prior notice and errors excepted. The data given in this sheet 
are accurately checked and refer to typical mass production values. The device descriptions and 
its applications, the fields of application, the external control details, as well as information on 
installation and operation, are provided to the best of our knowledge. This does not in any way mean 
that the characteristics described may entail legal liabilities extending beyond the “General Terms of 
Sale”, as stated in the Pizzato Elettrica general catalogue. Customers/users are not absolved from 
the obligation to read and understand our information and recommendations and pertinent technical 
standards, before using the products for their own purposes. Taking into account the great variety of 
applications and possible connections of the device, the examples and diagrams given in the present 
manual are to be considered as merely descriptive; the user is deemed responsible for checking that 
the specific application of the device complies with current standards. This document is a translation 
of the original instructions. In case of discrepancy between the present sheet and the original copy, 
the Italian version shall prevail. The present manual may not be reproduced, in whole or in part, 
without the prior written permission by Pizzato Elettrica.
© 2019 Copyright Pizzato Elettrica. All rights reserved.

Summary of Contents for CS AR-01 Series

Page 1: ...tuazioni pericolose Collegamento dei canali d ingresso a potenziali opposti Collegabile a circuiti d uscita a stato solido e sensori magnetici di sicurezza Funzione di rilevamento del cortocircuito degli organi di comando tramite sistema di sicurezza con autocontrollo e metodo di ridondanza Indicatori LED dello stato di commutazione dei canali 1 2 e della tensione d alimen tazione In caso di guast...

Page 2: ...Prima dell installazione assicurarsi che il dispositivo sia integro in ogni sua parte Prima della messa in servizio verificare il corretto funzionamento del modulo se guendo le indicazioni dei diagrammi di funzionamento vedi paragrafo FUNZIONA MENTO Evitare piegature eccessive dei cavi di connessione per impedire cortocircuiti e in terruzioni Non verniciare o dipingere il dispositivo Non forare il...

Page 3: ... 60 Hz art CS AR 01 024 120 Vac 50 60 Hz art CS AR 01 120 230 Vac 50 60 Hz art CS AR 01 230 10 30 Vdc art CS AR 01 E02 Tolleranza sulla tensione di alimentazione 15 di Un 10 di Un art CS AR 01 E02 Ondulazione residua max in DC 10 Assorbimento AC 5 VA Assorbimento DC 2 W 3 W art CS AR 01 E02 9 4 Circuito di controllo Protezione al corto circuito resistenza PTC Ih 0 5 A Tempi della PTC intervento 10...

Page 4: ...s situation Connection of input channels of opposite potentials Can be connected to semiconductor outputs and to magnetic safety sensors Short circuit detection function of the control elements by means of safety system with self monitoring and redundancy LED indicators for switching state of the channels 1 2 and for the power supply voltage In the event of a failure the device switches to a safe ...

Page 5: ... to prevent any short circuits or power failures Do not paint or varnish the device Do not drill the device Do not use the device as a support or rest for other structures such as raceways sliding guides or similar Before commissioning make sure that the entire machine or system complies with all applicable standards and EMC directive requirements The documents necessary for a correct installation...

Page 6: ...stance Ih 0 5 A PTC times Response time 100 ms release time 3 s Maximum resistance per input 50 Ω Current per input 40 mA Min duration of start impulse tMIN 100 ms 50 ms articles CS AR 01 E02 Response time tA 150 ms Release time tR1 15 ms Release time in absence of power supply tR 70 ms 100 ms articles CS AR 01 E02 Simultaneity time tC unlimited 9 5 Output circuit Output contacts 2 NO safety conta...

Page 7: ...ns intervention extérieure à condition que cela n entraîne pas de situation dangereuse Raccordement des canaux d entrée à potentiels opposés Associable à des circuits de sortie à l état solide et des capteurs magnétiques de sécurité Fonction de détection du court circuit des éléments de commande par système de sécurité avec autocontrôle et méthode de redondance Indicateurs LED de l état de commuta...

Page 8: ...rieurs qui y sont reliés et de leur typologie Avant l installation s assurer que le dispositif est totalement intact Avant toute mise en service vérifier le bon fonctionnement du module selon les diagrammes de fonctionnement voir paragraphe FONCTIONNEMENT S abstenir de plier les câbles de connexion de manière excessive afin d éviter les courts circuits et les coupures Ne pas vernir ni peindre le d...

Page 9: ...es selon EN 60947 1 9 3 Alimentation Tension d alimentation nominale Un 24 Vac dc 50 60 Hz art CS AR 01 024 120 Vac 50 60 Hz art CS AR 01 120 230 Vac 50 60 Hz art CS AR 01 230 10 30 Vdc art CS AR 01 E02 Tolérance sur la tension d alimentation 15 d Un 10 d Un art CS AR 01 E02 Ondulation résiduelle max DC 10 Absorption AC 5 VA Absorption DC 2 W 3 W art CS AR 01 E02 9 4 Circuit de contrôle Protection...

Page 10: ... Bedienereingriff möglich sein sofern dies nicht zu einer Gefährdungssituation führt Anschluss von Eingangskanälen mit entgegengesetzten Potenzialen An Halbleiterausgänge und magnetische Sicherheits Sensoren anschließbar Funktion zur Kurzschluss Erkennung der Befehlsgeber durch Sicherheits System mit Eigenüberwachung und Redundanz LED Anzeigen für den Schaltzustand der Kanäle 1 2 und für die Verso...

Page 11: ...glichkeit dass das Gerät keinen ausreichenden Personenschutz gewährt Die Sicherheits Kategorie des Systems gemäß EN ISO 13849 1 einschließlich der Sicherheits Vorrichtung hängt auch von den extern angeschlossenen Geräten und deren Typ ab Vor der Installation muss das Gerät inspiziert und auf seine Unversehrtheit geprüft werden Vor der Inbetriebnahme die korrekte Funktion des Moduls gemäß den Angab...

Page 12: ...rn 2 Stoßspannung Uimp 4 kV Bemessungsisolationsspannung Ui 250 V Überspannungskategorie II Luft und Oberflächenabstände gemäß EN 60947 1 9 3 Stromversorgung Nennversorgungsspannung Un 24 Vac dc 50 60 Hz Art CS AR 01 024 120 Vac 50 60 Hz Art CS AR 01 120 230 Vac 50 60 Hz Art CS AR 01 230 10 30 Vdc Art CS AR 01 E02 Versorgungsspannungstoleranz 15 von Un 10 von Un Art CS AR 01 E02 Max DC Restwelligk...

Reviews: