SELF-CLEANING & NO MAINTENANCE
The Plasma Air AutoClean 1560 is a self-cleaning, maintenance-free needlepoint
ionizer that produces positive and negative ions that neutralize harmful pollutants,
odors and pathogens (mold spores, bacteria and viruses). This compact self-cleaning
unit automatically removes dust and dirt build-up on the needles eliminating the need
for maintenance. It can be easily mounted at the fan inlet of any air handling system,
including RTUs, PTACs, mini-splits, fan coil units and VRF systems. The AutoClean
1560 includes a BAS terminal block for status and control. Unit accepts 12-24V
AC/DC without the use of an external power supply. The AutoClean 1560 is UL 2998
validated for zero ozone emissions.
MECHANICAL INSTALLATION INSTRUCTIONS
WARNING: Do not connect to power before mechanical installation is
complete.
1.
Included with the ionization unit is a mounting kit containing (4) self-tapping
screws, (2) magnetic strips to hold the unit in place and 6ft of 22ga power leads.
2.
Mount ionization unit to allow for future access.
3.
Mount the unit at or near the fan inlet using the slots in the mounting tabs, insuring
that air flows over the two needlepoint emitters simultaneously. Mount the ionizer
to the fan casing to avoid interference with the fan blades.
See Figures 1 & 2.
4.
The unit should be mounted downstream of the filter.
5.
For best results avoid locations directly downstream of a humidifier.
ELECTRICAL INSTALLATION INSTRUCTIONS
WARNING: Do not connect to power before installation is complete.
Always disconnect power to the unit before handling the ionizer.
1.
All field wiring to be in accordance with the National Electric Code Section 725
and authorities having jurisdiction.
2.
It is recommended that surge protection be installed with this ionizer at the
equipment level, building level, or circuit breaker panel feeding the product.
3.
If a step down transformer is used to feed the ionizer, the transformer must be
grounded.
4.
Do not install the ionizer on the same circuit as a UV Lamp or connect to the
same transformer as a UV Lamp.
5.
Connect power to ionizer using either 12V to 24V AC or DC.
See Figure 3.
6.
Connect power wires to power inlet fitting by pressing the orange tab firmly,
inserting the appropriate wire, then releasing the orange tab. Repeat as necessary
for the other wires. Strip wire insulation as necessary.
7.
For best results interlock ionizer power with fan control circuit.
8.
Apply power to the unit. The LED indicator will be green when power is applied to
the ionizer, but then turns orange when functioning properly.
FIGURE 1
A
IR
F
LO
W
TUNGSTEN AUTOCLEANING NEEDLEPOINT EMITTERS