4.
Optional Relay Configuration (relay by
others),
See Figure 7
. The unit can
provide form C Relay Contacts by
adding a DC relay. The relay is shown
with a EMF diode for protection of the
ionzer.
FIGURE 6
FIGURE 7
ZERO OZONE EMISSIONS -
MEASURED OZONE
EMISSIONS FROM PLASMA
AIR AUTOCLEAN 1560
DURING USE PHASE DOES
NOT EXCEED 0.005 PPM AS
TESTED BY UL 867
UL.COM/ECV
OPERATION
1.
When power is applied to the unit, the ionizer will be activated. The LED will
be green for several seconds indicating power has been applied to the ionizer.
2.
The green LED turns orange indicating the unit is in operation mode and ions
are being produced.
3.
Two minutes after initial startup, the LED changes back to green and the first
cleaning cycle is automatically initiated. After the cleaning cycle, the LED returns
to orange indicating proper operation.
4.
The cleaning cycle will repeat every 24 hours if unit operates continuously.
If fan doesn’t run continuously, steps 1 through 3 will repeat once the fan is
energized.
TROUBLESHOOTING
If the unit is not operating, check the following:
1.
Verify that all power connections are correct and tight. Reconnect any
loose wires as necessary.
2.
Verify that the supply fan is running to initiate operation, and that the
orange LED illuminates. If the LED is green, and cleaning cycle is not
active (wait afew minutes), contact Plasma Air for further support.