background image

MAINTENANCE

The main collection ESP cells and pre-filter should be washed regularly, depending on usage, or when the Fault 
indicator comes on. These 2 components should be soaked in soapy water. 
A water jet spray may be used to help remove the contaminants from the plates and pre-filter. Remove them, rinse 
and let it drip dry. 
NOTE: Do not use any brush or device to clean the plates or wires. Doing so may cause damage to the cells. Charcoal 
Filters, if used should be replaced every 3-4 months depending on usage. Failure to clean the ESP cells for an extended 
period of time may result in them being damaged. The UVC lamp is located between the fan and the charcoal filter. 
UV lights have a life span of 9000 hours.

SAFETY/WARNINGS

Ensure that all safety precautions are followed when using this electrical appliance. This IOM describes the safety 
precautions to be observed during operation to prevent injuries to yourself and others or damage to the device.

• 

To prevent electric shock, do not dismantle, repair or modify this product in any way. Maintenance and cleaning 
procedures shall be followed as described in this manual. In the case of unit’s malfunction, contact Plasma Air or 
our local manufacturer’s representative.

• 

Do not use in locations where flammable or explosive materials are stored.

• 

Do not subject the device to direct sunlight or high temperatures internal temperature rise in serious cases may 
cause fire and in mild cases may cause deformation of the outer casing. Stop operation when ambient temperature 
exceeds 110°F.

• 

Do not allow foreign objects into the device. High voltage components inside the device may cause electric shock. 
Children should not be allowed to touch or play near the device.

• 

To prevent fire or electric shock hazard, do not place the unit in wet places or where water may enter the unit.

• 

Do not use fabrics or other materials to cover this device. Obstructed air inlets and outlets will result in abnormal 
operation and may lead to fire or other accidents.

• 

To prevent electro-magnetic interference the device should be placed at least 3 feet away from computer, 
television or radio.

• 

For safety reasons and to prevent fire or electric shock, disconnect the power under the following conditions:

1. 

When you are not going to use the device for an extended period of time.

2. 

When cleaning or servicing the device.

3. 

When you move the device.  

TROUBLESHOOTING

• 

If the unit does not power on when you press the On/Off button on the remote control, check to make sure the 
batteries in the remote control are new and the door switch inside the filter panel is operable. If the unit still does 
not power on, check that the power cord is inserted fully into the outlet if these actions do not power the unit on, 
please contact Plasma Air or our local representative for further help.

• 

If the LEDs on the front panel illuminate, but the unit appears to not be functioning properly, turn the unit off, then 
depress the On/Off button for 5 seconds. This should reset the unit. If this does not solve the problem, contact 
Plasma Air or our local representative for further help.