*Exception for Horizontal Installations:
CANADA INSTALLATIONS:
A non combustible floor
protections extending beneath the flue pipe is required with
horizontal venting or under the top vent adapter with vertical
installation.
USA INSTALLATIONS:
A non-combustible floor protection
extending beneath the flue pipe is recommended with
horizontal venting or under the top vent adapter with vertical
installation.
A non combustible floor protector is required.
E. Hearth Pad Requirements (UL and ULC)
Use a non-combustible floor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance “M” from the surface of the
glass door.
USA Hearth Pad Requirements
Hearth Pad Requirements
Inches
K
Sides
2
L*
Back
2
M
Front
6
Canada Hearth Pad Requirements
Hearth Pad Requirements
Millimeters
K
Sides
203
L*
Back
51
M
Front
152
Must extend 2 inches (51mm) beyond each
side of pipe (shaded area)
L*
K
M
K
WARNING
!
If the information in these instructions is not
followed exactly, a fire may result causing
property damage, personal injury, or death.
•
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
•
Do not over fire - If heater or chimney connector glows,
you are over firing. Over firing will void your warranty.
•
Comply with all minimum clearances to combustibles
as specified.
Failure to comply may cause house fire.