Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications
Manual for 362MC
Page: 33
10 Technical data
Voltage supply
Standard
Optional
Input voltage
230V AC ±10%
115V AC ±10%
Frequency
50 - 60Hz ±5%
Stromaufnahme
max. 100mA (*
max. 200mA (* +switching current)
Permissible ambient temperature
Operating temperature
0 - +60°C
Storage temperature
-20 - +85°C
Protection type
Housing and terminals
IP00
Frontside
IP30
Housing
Type
Housing for installation in
Wall-mounting housing
Dimensions
144x72 mm acc.DIN 43700
Dimension sheet available
installation depth 140 mm on request
Control panel cut-out
137
+0.5
mm x 65.5
+0.5
mm
Weight
approx. 1200 g
Analogue inputs
(only 1
st
input)
(only 1
st
input)
1
st
and 2
nd
input (PT100 inputs)
Pt100
4 - 20mA
Measuring range
0 - 200°C
0 - 500°C
0-100%
Resolution
0.2°C
0.5°C
20µA
Measuring accuracy
±0.5%
3
rd
input (current/voltage input)
Measuring range
0(4) - 20mA
0 - 5V, 0 - 10V
Resolution
20µA
5 / 10mV
Measuring accuracy
±0.5%
Internal resistance
250 Ohm
4
th
input (resistance input)
Measuring range
0 - 200 Ohm
Resolution
0.2 Ohm
Measuring accuracy
±0.5%
Binary inputs
Type
6 x optocoupler inputs
for floating contacts
for 24V DC nominal inputs
(electrically isolated switching
(switching voltage external)
voltage supplied)
Operating threshold
12V ±4V
Switching current
1mA ±0.5mA
Switching outputs
Type
1 x relay set (expandable by 2
nd
relay set)
each with relay +(OPEN) and -(CLOSED)
Switching voltage
= supply voltage
floating contacts
(internal connected)
(external supply and fusing)
Max. contact current
1A at 230V-AC
max. 8A and max. 250V
2A at 115V-AC
purely resistive load only
Type
1 x alarm relay with floating changeover contact
Analogue outputs (hardware extension)
Type
2 x current output
2 x voltage output
Output range
0(4) - 20mA, ±20mA
0 - 10V, ±10V
Resolution
40µA
20mV
Accuracy
±0.5%
Load impedance
max. 400 Ohm
min. 1 kOhm
Communication interface (hardware extension)
Type
RS485 isolated
RS422 isolated