Warranty 

We reserve the right to make technical and formal changes to the product in the interest of technical 
progress.  Our products are under guarantee within the scope of the statutory provisions.  
If you have a warranty claim, please contact PLH by e@mail  (support@plhitalia.com) or the Local Reseller. 

 

© 2019 - epic srl - All rights reserved

Page    | 5

3

This product should not be disposed of with household waste.

Please recycle the products where facilities  
for electronic waste exist. Check with your local authorities for recycling advice. 

Please note!

•   The device may only be opened and installed according to 

the circuit diagram on the device or these instructions by a 

qualified electrician. The existing safety regulations must be 

observed.

•   Appropriate installation measures must be taken to achieve 

the requirements of protection class II.

•   This  independently  mountable  electromechani-

cal  or  electronic  device  is  designed  for  controlling  the 

temperature in dry and enclosed rooms only under normal 

conditions.

•   The device confirms to EN 60730, it works according opera-

ting principle 1C.

•   The permissible relative humidity of max. 95% must not be 

exceeded. Condensation is to be avoided.

•   When  starting  up  the  room  temperature  controller,  it 

must be noted that the thermo-bimetal requires a  certain 

period of time to adapt itself to the room temperature. The 

switching point will therefore deviate from the room tem-

perature immediately after installation or after switching off 

the night set-back. The switching point accuracy is ensured 

after approx. 1 to 2 hours of operation. 

   To  heat  up  faster  in  the  beginning  and  shorten  the  com-

pensation  time  in  the  beginning,  we  recommend  setting 

the  room  temperature  higher  than  actually   desired.  After 

attaining the  temperature, the temperature setting can be 

set back to the desired setpoint value.

Applications

•   The room temperature controller controls the temperature 

in  closed  rooms,  such  as  apartments,  schools,  halls,  work-

shops, etc. subject to normal  ambient conditions.

Installation location

•   Preferably opposite the heating source on an inside wall.

radiator

radiator

Room

Temperature Controller

•   Installation height: approx. 1.5 m above the floor
•   Avoid outside walls and air drafts originating from windows 

and doors.

•   Please observe that the normal convection  air of the room 

must  be  able  to  reach  the  controller  without  hindrance. 

The  controller  should  therefore  not  be  installed   between 

shelves, behind curtains or be covered  in any way.

•   Heat from other sources has a negative influence on cont-

roller accuracy.

Therefore you should avoid:

   direct  sunlight,  installation  in  the  vicinity  of  TVs,  radios, 

heaters, lamps, chimneys, and heating ducts.

•   Even a dimmer creates heat!
   If  the  controller  and  a  dimmer  are  installed  in  a  shared 

switch frame, the devices should be placed as far apart from 

each  other  as  possible.  If  the  devices  are  installed  above 

each other, the controller must be below the dimmer on the 

bottom.

Installation on 58mm flush-type box  (DIN 49 073)

a)  Remove casing cover:
  - Pull off the adjustment knob

  - Loosen the cover screw

  - Pull off the cover

b)  Electrical  connection  according  to  circuit  diagram 

(see below).

c)  Mount the device onto the socket using the  thread-forming 

tapping screws for flush-type boxes.

d)  Mount the casing cover with switch frame.
The cover must latch into the bottom part of the casing before 

tightening the screw.
  - Push the adjustment knob back on
To  facilitate  dismantling,  the  casing  cover  and  switch  frame 

should be removed together.

Electrical connection

Connect  all  lines  exactly  as  shown  in  the  relevant  circuit 

diagram.
Please observe that the neutral conductor N is connected to 

terminal N. If this is not the case, large temperature deviations 

will  result  since  the  controller  will  not  be  able  to  function 

properly.
Conductor cross-section: 1 mm2 to 2.5 mm

2

 solid conductor

No protective-conductor terminal is required since the device 

is completely insulated.

Brief description in the circuit diagram

= outer conductor (phase)

= neutral conductor (previously Mp)

>

  =  terminal for clock signal for  

temperature set-back

U

  = heating load terminal

P

  = cooling load terminal

RF  = resistance for thermal feedback
TA  =  resistance for night set-back of room temperature

Technical data

Type

2026..

2030..

2031..

Temperature range

5…30 °C  5…30 °C

5…30 °C

Rated voltage

AC 250 V  AC 250 V 

AC 24 V

Rated current

 (cos 

ϕ

 

= 0,6)
   

U

 heating

   

P

 cooling

10 (4) A
  5 (2) A

10 (4) A

(DC 24V)
10 (4) A

Switching capacity
   

U

 heating

   

P

 cooling

2,2kW
1,1kW

2,2kW

240 W*

Switching temp. diff.

app. 0,5 K app. 0,5 K

app. 0,5 K

Night set-back

app. 4 K

app. 4 K

*At DC max. 100 W

For all devices:
Degree of pollution

2

Calculation impulse voltage

4 kV

Temperature for the Ball compression test 

75 ± 2 °C

Voltage and Current for the for purposes 

of interfernce measurements

230 V, 10 A

Order No.: 2030 .. 

 Room temperature controller 250 V 

with  NC contact, On/Off switch and 

LED

Order No.: 2031 .. 

 Room temperature controller 24 V 

with  NC contact, On/Off switch and 

LED

 

Note:

 

LED  On = controller active

Order No.: 2026 ..  Room temperature controller 250 V with

 

changeover contact

Narrowing down the temperature setting range

The  controller  is  factory-set  to  a  maximum  setting  range  of 

5 °C to 30 °C (see Fig. 1).
There  are  2  ring  gauges  in  the  adjustment  knob. These  ring 

gauges can be used to narrow down the temperature setting 

range as required, for example to a range of 8 °C to 23 °C.

Setting procedure:

1. Select the temperature limits:
  Example: max. 23°C        min. 8°C
2.  Note!  First  turn  the  adjustment  knob  to  the  approximate 

average value in the middle of the desired setting range.

  Example:  The  average  value  between  8°C  and  23°C  is 

approx. 15°C

3.  Then pull off the adjustment knob.
4.  Set  the  red  ring  gauge  to  the  max.  temperature  limit. 

Example: 23°C

Rotate counter-clockwise. The numbers on the outside of the 

scale are valid! Place the tip of a pen   into the hole and rotate 

the red ring  counter-clockwise to 23°C (max. scale Fig. 2).
5.  Set the blue ring gauge to the minimum temperature  limit.
  Example: 8°C
Rotate clockwise. The numbers on the inside of the scale are 

valid! Place the tip of a pen into the hole and rotate the blue 

ring to 8°C (min. scale Fig. 3).
6.  Push the adjustment knob back on:
The indicator must be approximately in the center of the new 

setting range; see 2. 
Example: approx. 15°C

Fig. 1

The controller is supplied

with this setting

Full range:

5°C to 30°C

 

Fig. 2

Red gauge ring (max.)

set in direction of arrow

to 23°C

 

Fig. 3

Blue gauge ring (min.)

set in direction of arrow

to 8°C

 

Temperature setting scales

with flag digits

P

 = approx.   5°C 

 

= approx. 20°C

2

  = approx. 10°C 

5

  = approx. 25°C

3

  = approx. 15°C 

6

  = approx. 30°C

Symbols

  OFF

    

ON

ê

  permanently set temperature

ë

  permanently set set-back temperature

N

   switch-over  between  day  and  night  temperature 

controlled by time switch

Warranty

We reserve the right to make technical and formal changes to 

the product in the interest of technical progress. 
Our  products  are  under  guarantee  within  the  scope  of  the 

statutory provisions. 
If you have a warranty claim, please contact the point of sale or 

ship the device postage free with a description of the fault to 

the appropriate regional representative.

Operating Instructions

Room

Temperature Controller

Order No. 2026 .., 2030 .., 
2031 ..

46

8

93

1

02

2

976-2

     

 9709182000

This product should not be disposed of with 

household waste.
Please  recycle  the  products  where  facilities 

for  electronic  waste  exist.  Check  with  your 

local authorities for recycling advice.