background image

IP-010 

 

Page 

10

 of 

13

 

Revision 3 

into the gap between the PLIDCO Clamp+Sleeve and the pipe towards the seals.  The flame from a 
preheat torch is helpful in burning off oils and other contaminates.  Do not use a large torch, commonly 
called a rosebud, because of the difficulty controlling the size of the area being preheated. 

Monitor the heat generated by welding or preheating, particularly near the area of the seals, by using 
temperature crayons or probe thermometers.  If the heat generated approaches the temperature limit of 
the seal material, which is indicated on the label, welding should be discontinued or sequenced to another 
part of the fitting so that the affected area has a chance to cool. 

Seal welding the grade B-7  studs of the PLIDCO Clamp+Sleeve is the most difficult phase of field 
welding.  They are made of AISI 4140 steel with a high carbon equivalence.  By using a low hydrogen 
welding process with preheat, the problem of hydrogen cracking and pinholes can be reduced.  The 
preheat will dry out any moisture, oil dampness or thread lubricant that may be present in the weld area.  
If the stud lengths need to be cut back, allow at least 1/4 inch (6.4 mm) of stud beyond the nut for the 
fillet weld.  Preheat the stud and nut, and then weld the nut to the stud.  Check the preheat and then weld 
the nut to the sidebar. 

 

WELDING AFTER A CONSIDERABLE TIME LAPSE AFTER THE INITIAL INTALLATION 

PLIDCO recommends that if the PLIDCO Clamp+Sleeve is to be welded, the welding be completed as 
soon as possible after the installation; as conditions permit.  Welding at a significantly later date relies 
heavily on whether proper installation procedures were followed and the compatibility of the elastomeric 
gaskets with the product in the pipeline. 

After the installation of the PLIDCO Clamp+Sleeve there is no meaningful test that can be performed to 
determine the condition of the gaskets or the remaining service life the gaskets.  There are many 
variables that can affect the condition of the gaskets over which PLIDCO has no control. 

If the PLIDCO Clamp+Sleeve is to be welded at a significant time lapse from the installation, the follow 
precautions should be followed: 

1. 

The PLIDCO Clamp+Sleeve must be closely inspected for any leakage that may have developed. 

2. 

The studs and nuts should be retightened per the recommended torque value. 

3. 

If possible, the pressure in the line should be reduced. 

4. 

Some flow in the line is still required to dissipate the welding heat to prevent damage to the 
elastomeric seals. 

5. 

Following the recommended welding practices as listed under Field Welding Instructions. 

Welding Sequence 

Caution should be observed so that welding does not overheat the seals.  Sequence the welding so that 
the heat is not concentrated in one area.  It will be necessary to re-torque the studs and nuts periodically 
during field welding because weld contraction causes them to loosen. 

1. 

Fillet weld ends to pipe.  (See Figure 12) 

2. 

Seal Weld side openings. 

3. 

Re-torque studs and nuts. 

4. 

Seal weld nuts to studs. 

5. 

Seal weld nuts to sidebars. 

6. 

Seal weld vent plugs, if applicable. 

Summary of Contents for CLAMP+SLEEVE

Page 1: ...SH PLIDCO CLAMP SLEEVE INSTALLATION INSTRUCTIONS LANGUAGES CLICK ON LANGUAGE DESIRED PLIDCO The Pipe Line Development Company www plidco com 440 871 5700 pipeline plidco com 11792 Alameda Drive Strongsville OH 44149 ...

Page 2: ... standards If the PLIDCO Clamp Sleeve is to be installed underwater be sure to read the Underwater Installation section Whenever a PLIDCO product is modified in any form including adding a vent or changing seals by anyone other than the Engineering and Manufacturing Departments of The Pipe Line Development Company or a PLIDCO certified repacking company the product warranty is voided Products that...

Page 3: ...nel should not be allowed near the repair until the seal has been proven Pipe Preparation 1 Remove all coatings rust and scale from the pipe surface where the circumferential seals and clamping sections of the PLIDCO Clamp Sleeve will contact the pipe A near white finish as noted in SSPC SP10 NACE No 2 is preferred at location where the seals contact the pipe The cleaner the pipe surface the more ...

Page 4: ... provided both lifting eyes are required to lift the fitting Chains hooks shackles or straps suitable for the weight of the fitting s shall be used and must be securely inserted through the lifting eyes The lifting eyes are designed to support the weight of a fully assembled Clamp Sleeve The lifting eyes are installed on both halves of the fitting and should be used to maneuver or lower Clamp Slee...

Page 5: ...th a lubricant Table 1 lists the lubricants that are recommended for the various seals The customer must determine if the lubricant is compatible with the product in the pipeline Lubricant is not recommended for underwater installations or for braided packing Refer to the section on Underwater Installations Petroleum based lubricants A Silicone based lubricants B Glycerin based lubricants C Super ...

Page 6: ...s per side in the seal area insert the longer studs in the center holes For PLIDCO fittings with more than 3 holes per side in the seal area insert the longer studs in the four corner holes Sometimes it is helpful to loosely assemble the PLIDCO Clamp Sleeve to one side of the leak then reposition it centered over the leak 5 Torque all of the studs and nuts on the PLIDCO Clamp Sleeve uniformly usin...

Page 7: ... To complete assembly ALL studs should be rechecked at the recommended torque Torque all studs in a circular pattern at 100 torque all studs and nuts are unable to continue spinning Keep in mind an increase in torque on one stud can cause a decrease in torque on neighboring studs Note The torque values listed on the PLIDCO Torque Chart represent residual torque The initial torque value may need to...

Page 8: ...ch shackles to the lifting eyes Smaller fittings typically only have lifting eyes in the center of the shell as shown in Figure 8 Larger diameter fittings have additional lifting eyes on an angle as shown in Figure 9 For larger diameter fittings the angled lifting eyes are to be used during installation with hinges Figure 8 Figure 9 3 Attach properly sized rigging such as chains cables or straps t...

Page 9: ...0 Figure 11 Sealant Injection Sealant Injection is not required for a PLIDCO Clamp Sleeve to achieve a leak tight seal provided the sleeve was installed with elastomer seals was installed per this installation instructions and the temperature and pressure of the pipeline are within the design limitations of the PLIDCO Clamp Sleeve However PLIDCO Clamp Sleeves are capable of being injected with sea...

Page 10: ...ice welding must be considered when planning in service welding Refer to IP 019 Welding Considerations for additional information It is recommended that the pipeline should be full and under flow Welders and weld procedures should be qualified in accordance with API Standard 1104 Welding of Pipelines and Related Facilities Appendix B In Service Welding We strongly recommend the use of a low hydrog...

Page 11: ...eve is to be welded the welding be completed as soon as possible after the installation as conditions permit Welding at a significantly later date relies heavily on whether proper installation procedures were followed and the compatibility of the elastomeric gaskets with the product in the pipeline After the installation of the PLIDCO Clamp Sleeve there is no meaningful test that can be performed ...

Page 12: ...ommended Inspection Schedule 1 After the pipeline is re pressurized and field tested see Re pressuring and Field Testing for precautions the torque values should be checked again 4 hours after installation Then the torque values should be checked again 24 hours after that 2 It is recommended that if the product is not being welded that torque striping be applied from the nuts to the sidebar of the...

Page 13: ...t product is exceeded causing leakage or damage to the fitting The pipe on which the fitting is installed is damaged Personal injury or death due to subsequent removal of a vent plug RECOMMENDATIONS The Pipe Line Development Company strongly recommends the following for all underwater installations 1 Order or procure fittings with vents 2 Leave the vents open during installation Additionally the P...

Page 14: ... 37 500 psi pre stress 4 1 4 6 1 2 16300 22100 32500 44100 4 1 2 6 7 8 19400 26300 38700 52500 4 3 4 7 1 4 22900 31000 45600 61900 5 7 5 8 26700 36300 53300 72300 5 1 4 8 31000 42100 61900 83900 5 1 2 8 3 8 35700 48400 71200 96600 5 3 4 8 3 4 40900 55400 81500 110600 6 9 1 8 46500 63000 92800 125800 Studs ASTM A193 Grade B7 Nuts ASTM A194 Grade 2H Note 1 The torque values listed are residual torqu...

Page 15: ...SPANISH INSTRUCTIONS COMING SOON ...

Reviews: