①、

block protection

When working current reaches to from 4 times to 8 times of set current after finish 

starting, response time 

0.2s

 

②、

Short circuit protection: when testing current reaches above 8 times of set current, response time

0.2s

 

③、

Protection of phase failure: in case of phase failure of any one phase,

 operation time equals 

setup time

                                   

④、

Unbalance protection: when currents of any two phase differ 60

75%,

operation time equals 

set time

                                     

⑤、

Protection  characteristics  of  reverse time  limit  of  overload (time unit:  second)

please  see  following 

table

table 2.1.1

),

multiple

Iactual

Iset 

              motor operates with delay time according to overload factors and operation time shown in following table 

(table  2.1.1)  when  motor’s  working  current  is  larger  or  equal  to  from  1.2  times  and  3.0  times  of  set 

current. 

         

I

actual

/

I

set 

 

Time parameters 

 

1.2 

≥1.3

 

≥1.5

 

≥1.6

 

≥2.0

 

≥3.0

 

Operation time

S

  60 

48 

24 

Table 2.1.1 curve table of reverse time limit for protection of motor

 

8、

Temperature protection: when actual temperature measured is larger than temperature set; response time

2s

; 

9、

Contact capacity of output relay: 250V,5A

Contact endurance 500000 times

 

10、

Error of displayed current is less than 1.0%.

; 

11、

RS485 communication 

3

  Type and specification 

1、 Instruction of type 

 

2、Specification table for power of suited motor 

MAM 880

B

T

 

V

40

   

Maximum  working  current  matching 
with host motor

With voltage detection 

With RS485 communication 

B: pressure sensor; K: Pressure switch 

880 controller 

Serial 

Summary of Contents for MAM-880

Page 1: ...hen Plot electronic Co Ltd Address Sixth floor twenty fifth building TIAN JIAN industrial estate SHANG BAO road FU TIAN district SHEN ZHEN Telephone 0755 83172098 83172068 Postal code 518034 Fax 0755...

Page 2: ...lly before switch up Earthing terminal of this body part shall be earthed correctly the third type of earthing to increase product s capacity of resisting signal noise Motor s rated current current fo...

Page 3: ...matic control 17 3 Local manual control 17 4 Remote Manual Control 17 5 Network control 17 6 Temperature control of fan 18 7 Failure shutdown and emergency shutdown 18 6 Early warning and prompts 18 1...

Page 4: ...d by pressing this button when data are modified Menu is moved upwards when menu is selected Move down button Descending button Data at current position is descended by pressing this button when data...

Page 5: ...to move the black cursor to RUN PARAMETER press enter button to pop up submenu WELCOME USING SCREW COMPRESSOR AIR T 20 AIR P 0 60MPA NORMAL STOP C001 REMOTE RUN PARA USER PARA FACTORY PARA CALBR PARA...

Page 6: ...rimary menu press the move button to move the black slider to the USER PARA menu press the shift button to switch to the following menu Move the cursor to the P T SET menu then press enter button to s...

Page 7: ...P Control the stopping of the fan TIME SET HOST START 0008S When using the controller to protect the motor it is required that the time set here will not meet the impulse starting current of the motor...

Page 8: ...ration SEQ LOAD MPa The main air compressor searches for one device in the interlocking network for loading or starting when main air compressor s gas supply pressure is less than the value set here d...

Page 9: ...press set button switch to the factory parameters of the interface as follows Factory parameters run time phase sequence protection Frequency Selection and the time need check super password to chang...

Page 10: ...er frequency HIGH VOL V Controller detects the voltage higher than the set value the shutdown protection reported voltage is too high Set this value to 0000 the high voltage function is no function LO...

Page 11: ...A Displays the current controller sampling current values This value is the real value can not be set F A N A TARGET CUR 0000 Enter the current value the controller will detect user input value divide...

Page 12: ...cturers Password factory fixed ___________ Permissions Allows users to modify all the parameters the user password and the parameters of some manufacturers manufacturers selling password 6 Calibration...

Page 13: ...ors and operation time shown in following table table 2 1 1 when motor s working current is larger or equal to from 1 2 times and 3 0 times of set current Iactual Iset Time parameters 1 2 1 3 1 5 1 6...

Page 14: ...15 50 MAM880 200 80 200 40 100 MAM880 400 160 400 80 200 MAM880 600 5 100 600 50 300 4 Installation 1 Installation of transducer The transducer shall be installed at place where motor s line current...

Page 15: ...l dimensions of CT2 2 Controller Installation The controller is installed as plate Room should be left around controller for wiring The specific dimensions are as follows Figure 4 1 5 Controller struc...

Page 16: ...fan 15 terminals controls load valve 16 terminals controls angle shaped contactor 17 terminals controls star shaped contactor 18 terminals controls main contactor NOTE Eelectromagnetism coil shall be...

Page 17: ...ding until gas supply pressure is less than loading pressure If pressure is less than loading pressure the unloading button do not function Normal shutdown Press the button the load magnetic valve wil...

Page 18: ...filter Early warning for blockage of oil filter The controller can display the message on the text display to remind the operator that the air filter is blocked by checking the pressure difference swi...

Page 19: ...T 3 Non reversing Protection of Air Compressor When three phase supply phase sequence connected to the air compressor is not the same with that set for the controller the on site failure is displayed...

Page 20: ...power and contactors Overloaded Voltage too low tubes blocked Bearing Wear off or other mechanical failure or wrong set data etc Check the set data Voltage bearings tubes and other mechanical system...

Page 21: ...Temperature too high Bad vent condition Oil lacking etc Check the vent condition and lubricant amount etc Temperature Sensor Failure Cable off or PT1OO damaged Checking the wiring and PT100 Over Pres...

Page 22: ...Page 22 of 22 9 Electrical diagram 18 17 16 15 14 13 uc ua ub C1 RS 485 B A 1 FG 22 23 24 25 26 27 28 29 30 31 a CT2 21 20 19 2 3 4 5 6 7 8 9 10 b c A B C CT1 11 12...

Reviews: