background image

12

11

CT1

C

B

A

c

b

1

0

9

8

7

6

5

4

3

2

19

20

21

CT2

a

3

1

3

0

2

9

2

8

2

7

2

6

2

5

2

4

2

3

2

2

FG

1

A

B

RS-485

C1

ub ua

uc

13 14 15 16 17 18

 

Figure 4.2.1

 

Terminal arrangement diagram 

Terminal blocks of controller

 

        1  is  common  terminal  COM1

2  is  input  terminal  for  emergent  stop  signal

  3  is  remotely  controlled for 

on/off signal input terminal

4 terminal is used to detect oil filter blocked

  6 is RS485 A; 7 is RS485 B

8 is the 

simulated ground (Earth)

17 and 18 are the AC20V power source

22

23 terminals are Pressure Sensor signal 

input

24

25

26 terminals are motor mutual inductor CT1 input

27

28

2 terminals are Fan mutual inductor 

CT2 input

30

31 terminals are Temperature Sensor signal input

19

20

21 terminals Used to detect the phase 

sequence and voltage

13 terminals is common terminal of output relay

14 terminals controls fan

15 terminals 

controls load valve

16 terminals controls angle-shaped contactor

17 terminals controls star-shaped contactor

18 terminals controls main contactor

 

NOTE:  Eelectromagnetism  coil  shall  be  connected  with  surge  absorber  during  wiring,  and 
dotted lines are extendable functions. 

5

  Control principles 

1、Local Automatic control  

. press down start button for starting:    (Y-

start) 

There  is  fives  of  self-test  after  controller  is  energized  and  it  can  not  be  started  by  pressing  start 

button  .The  air  compressor  starts  by  pressing  start  button  after  self-test  finished.  The  course  of 

compressor’s 

start as followed: KM3 and KM2 are energized → Y

-

type status of start    → delay time

 is 

reached    (Y-

change-over time);  KM3 is de-energized  (KM1 and KM3 are interlocked) and KM1 is 

energized    →  motor  operates  with 

  type  to  finish  start.  During  the  course  of  starting,  all 

electromagnetism valves are de-energized to achieve no load start. 

. Automatic operation control: 

When  the  motor  is  started  to  running  in 

  status  and  load  the  magnetic  valve  with 

Summary of Contents for MAM-880

Page 1: ...hen Plot electronic Co Ltd Address Sixth floor twenty fifth building TIAN JIAN industrial estate SHANG BAO road FU TIAN district SHEN ZHEN Telephone 0755 83172098 83172068 Postal code 518034 Fax 0755...

Page 2: ...lly before switch up Earthing terminal of this body part shall be earthed correctly the third type of earthing to increase product s capacity of resisting signal noise Motor s rated current current fo...

Page 3: ...matic control 17 3 Local manual control 17 4 Remote Manual Control 17 5 Network control 17 6 Temperature control of fan 18 7 Failure shutdown and emergency shutdown 18 6 Early warning and prompts 18 1...

Page 4: ...d by pressing this button when data are modified Menu is moved upwards when menu is selected Move down button Descending button Data at current position is descended by pressing this button when data...

Page 5: ...to move the black cursor to RUN PARAMETER press enter button to pop up submenu WELCOME USING SCREW COMPRESSOR AIR T 20 AIR P 0 60MPA NORMAL STOP C001 REMOTE RUN PARA USER PARA FACTORY PARA CALBR PARA...

Page 6: ...rimary menu press the move button to move the black slider to the USER PARA menu press the shift button to switch to the following menu Move the cursor to the P T SET menu then press enter button to s...

Page 7: ...P Control the stopping of the fan TIME SET HOST START 0008S When using the controller to protect the motor it is required that the time set here will not meet the impulse starting current of the motor...

Page 8: ...ration SEQ LOAD MPa The main air compressor searches for one device in the interlocking network for loading or starting when main air compressor s gas supply pressure is less than the value set here d...

Page 9: ...press set button switch to the factory parameters of the interface as follows Factory parameters run time phase sequence protection Frequency Selection and the time need check super password to chang...

Page 10: ...er frequency HIGH VOL V Controller detects the voltage higher than the set value the shutdown protection reported voltage is too high Set this value to 0000 the high voltage function is no function LO...

Page 11: ...A Displays the current controller sampling current values This value is the real value can not be set F A N A TARGET CUR 0000 Enter the current value the controller will detect user input value divide...

Page 12: ...cturers Password factory fixed ___________ Permissions Allows users to modify all the parameters the user password and the parameters of some manufacturers manufacturers selling password 6 Calibration...

Page 13: ...ors and operation time shown in following table table 2 1 1 when motor s working current is larger or equal to from 1 2 times and 3 0 times of set current Iactual Iset Time parameters 1 2 1 3 1 5 1 6...

Page 14: ...15 50 MAM880 200 80 200 40 100 MAM880 400 160 400 80 200 MAM880 600 5 100 600 50 300 4 Installation 1 Installation of transducer The transducer shall be installed at place where motor s line current...

Page 15: ...l dimensions of CT2 2 Controller Installation The controller is installed as plate Room should be left around controller for wiring The specific dimensions are as follows Figure 4 1 5 Controller struc...

Page 16: ...fan 15 terminals controls load valve 16 terminals controls angle shaped contactor 17 terminals controls star shaped contactor 18 terminals controls main contactor NOTE Eelectromagnetism coil shall be...

Page 17: ...ding until gas supply pressure is less than loading pressure If pressure is less than loading pressure the unloading button do not function Normal shutdown Press the button the load magnetic valve wil...

Page 18: ...filter Early warning for blockage of oil filter The controller can display the message on the text display to remind the operator that the air filter is blocked by checking the pressure difference swi...

Page 19: ...T 3 Non reversing Protection of Air Compressor When three phase supply phase sequence connected to the air compressor is not the same with that set for the controller the on site failure is displayed...

Page 20: ...power and contactors Overloaded Voltage too low tubes blocked Bearing Wear off or other mechanical failure or wrong set data etc Check the set data Voltage bearings tubes and other mechanical system...

Page 21: ...Temperature too high Bad vent condition Oil lacking etc Check the vent condition and lubricant amount etc Temperature Sensor Failure Cable off or PT1OO damaged Checking the wiring and PT100 Over Pres...

Page 22: ...Page 22 of 22 9 Electrical diagram 18 17 16 15 14 13 uc ua ub C1 RS 485 B A 1 FG 22 23 24 25 26 27 28 29 30 31 a CT2 21 20 19 2 3 4 5 6 7 8 9 10 b c A B C CT1 11 12...

Reviews: