14
OI remote control for Pluggit Avent
Setting the period
1. With the night setback switched on, press the bottom of
button (1).
The display (3) starts flashing and the starting time can
be set.
2. Press top or bottom of button (1) until the desired
starting time is selected.
3. Press centre of button (1).
The setting of the starting time is saved and the end time
appears on the display (3).
4. Press top or bottom of button (1) until the desired end
time is selected.
5. Press centre of button (1).
The setting of the end time is saved.
Switching off
Press centre of button (1).
The display (2) turns off.
3.8.
SWITCHING ON/OFF THE FIRE BOOSTER
When initiating a fireplace, such as a fireside, the fire
booster can be switched on.
With the fire booster switched on, the supply air ventilator is
set to level 3. The room ventilation unit operates at the
nominal volume flow rate. The supply air ventilator oper-
ates at a speed of 100 % and the exhaust air ventilator at a
speed of 50 %.
If the supply air temperature (T2) falls below 9 °C before the
period of 7 minutes has expired, the room ventilation unit
automatically switches back to the last operating mode. The
unit operates again at the speed of the previous operating
mode.
Hold down the top of button (1) for approx. 5 seconds until
FP7 appears on the display (2).
The fire booster will be switched on for 7 minutes and the
display (2) counts down (FP6...FP01).
After the time has expired, the room ventilation unit auto-
matically switches back to the last operating mode.
3.9.
SETTING/SWITCHING ON BAYPASS (OPTIONAL)
The bypass is available as an accessory. It allows bypassing
the heat exchanger and thus, the cooler outside air is not
heated.
There are two versions of the bypass available.
•
Version A is an exhaust air bypass. The exhaust air by-
passes the heat exchanger and thus, the supply air is not
heated.
•
Version B is a supply air bypass. The supply air bypasses
the heat exchanger and thus, the supply air is not
heated.
3.9.1.
Setting automatic bypass
The automatic bypass can be used at night in summer for
example. The outside temperature must be higher than
15 °C , but must be lower than the room air temperature.
In the installer menu, the temperatures can be set from
T
min
and T
max
, see page 17.
T
min
indicates the lower operating limit for the functioning
of the bypass. Thus, any draughts in the rooms and conden-
sate formation are avoided.
T
max
indicates the functioning of the bypass with regard to
the exhaust air temperature at which the bypass opens for
cooling (summer mode).
The bypass is automatically activated when:
•
the outside air is 2 °C lower than the supply air and
•
T
min
is exceeded and
•
T
max
is exceeded.
3.9.2.
Manually switch on and off bypass
At lower outside temperatures, e.g. in spring or autumn, the
building can be cooled down by manually switching on the
bypass, without a heat recovery being used.
The bypass will then be activated for 6 hours, as long as the-
temperature difference of 2 °C between of the outside air
and the supply air continues to be present.
Die Wohnraumlüftung
RH%
2
1
M+P-26A-0974
Note:
The fire booster cannot be operated at outside tempera-
tures below -13 ° C. For this purpose, installing a pre-
heating is required (accessory).