4
OI remote control for Pluggit Avent
4
Info line
5
Time/weekday
Controlling the week timer and night setback
6
Operating modes
7
Operating data
•
Outdoor temperature (T1)
•
Supply air temperature (T2)
•
Exhaust air temperature (T3)
•
Outgoing air temperature (T4)
•
Indoor air temperature (T5)
Alarm
Room ventilation unit error in connection
with the display of an error code.
Information on functions, programmes and
error codes
A1
Automatic programme
P1, P2...
Weekly programme
BYP6, BYP5...Manual bypass switched on.
FP7, FP6...
Fire booster switched on
DEF
Defrost function
E1, E2...
Error codes
Niedriger Batteriestatus
Automatic programme
Manually select ventilator level
Selecting weekly programme
Switching on/off holiday mode
Switching on/off night setback
Filter change
Reset filter alarm
Relative air humidity of the exhaust air
(optional)
A humidity sensor must be installed and the
automatic mode must be switched on to con-
trol the room ventilation unit depending on the
relative air humidity.
<24 % relative humidity
Very dry air, ventilator level 1
25-34 % relative humidity
Dry air, ventilator level 1
35-45 % relative humidity
Comfort range, ventilator level 1-3
46-65 % relative humidity
Comfort range, ventilator level 3
>66 % relative humidity
Humid air, ventilator level 3
VOC content of the air
(optional)
A VOC sensor must be installed and the auto-
matic mode must be switched on to control
the room ventilation unit depending on the
VOC content.
<600 ppm
Clean air, ventilator level 1
600-850 ppm
Clean air, ventilator level 1-2
850-1100 ppm
Sufficient air quality, ventilator level 2-3
1100-1200 ppm
Sufficient air quality, ventilator level 3
1200-1600 ppm
Slightly polluted air, ventilator level 3
>1600 ppm
Polluted air, ventilator level 4
Preheat temperature
(optional)