Automist Smartscan
®
Handbook v1.2.3
Plumis Ltd Copyright © 2017. All Rights Reserved.
Page 27 of 64
S MA RT SC AN
®
Automist Smartscan Known Heat Source Mitigation Procedure
Object Type
Positional Constraints
Radiator or heated towel rail, within 180° field of
view of spray head, with height less than 800mm
No constraints.
Radiator or heated towel rail, within 180° field of
view of spray head, with height above 800mm
No point on the radiator must be closer than 3.0m
from any spray head. Spray heads may be
permitted to be closer to the radiator when
mounted on the same flat wall as the radiator, but
still no closer than 1.0m.
Real fire, gas fire, or electric heater with exposed
heating elements
No spray head should be mounted in a position
whereby the flames or heating elements are in view
of the spray head, at any distance. Walls of any
visibly opaque construction can be regarded as
blocking this view.
Cooker hob or oven
Spray heads must be located at least 2.5m distant
from any cooker hob or oven that is in view of the
spray head’s sensor.
The spray head can be
installed in the same wall as the hob or oven 2m
away.
Table 2: Known heat source mitigation procedure