In addition to the alarm relay input cable, Smartscan head cable and the power cable at the rear of the unit,
the pump features a single core loop cable. This is to allow an auxiliary (external) STOP button to be added,
for example if the pump is installed enclosed in a space where the STOP button is inaccessible. Where
required, the loop should be cut and each end of the wire connected via FP200 or equivalent cable to a
momentary action, normally closed, push button switch (see diagram above). The button should have an
appropriate IP rating (e.g. IPX5 if used in the room protected by Automist Smartscan), located as close to
the pump as possible and should be clearly labelled. The auxiliary button cannot be used to commission
the unit but can be used to enter ALARM TEST MODE (see page 49). Technical notes on suitable buttons are
available from the Plumis Partner Site.
Butt splice pliers
Butt splice clips