S MA RT SC AN
®
Problem
Probable Cause
Recommended Action
Either the
pressure is
above the
correct range,
or the pump
pulses or
temporarily cuts
out during the
commissioning
test
High pressure
blockage
Disconnect high pressure hose between the Automist
Smartscan head and the pump and check for blockages in
the high pressure line or around the inlet to the spray head.
Warranty
Plumis Ltd warrants its products to be free from defects in materials and workmanship under normal
residential use for a period of two years from the date of original purchase. If annual servicing is kept up to
date, then this warranty is extended to four years. This warranty is limited to repair or replacement of units
returned to Plumis Ltd according to our return procedure. The warranty on any replacement units, will last
for the remainder of the period of the original warranty. Plumis Ltd reserves the right to offer an alternative
product similar to that being replaced if the original model is no longer available or in stock.
If the product is found to have failed for reasons outside our warranty cover Plumis may quote to repair the
unit and return it. Where products are replaced or repaired under warranty, they will be returned to a UK
address free of charge.
This warranty does not cover the removal or reinstallation of products, or faults in installation.
Plumis Ltd shall not be liable for any incidental or consequential damages caused by the breach of any
expressed or implied warranty. Except to the extent prohibited by applicable law, any implied warranty of
merchantability or fitness for a particular purpose is limited in duration for two years. This warranty does
not affect your statutory rights.