Automist Smartscan
®
Handbook v1.2.3
Plumis Ltd Copyright © 2017. All Rights Reserved.
Page 59 of 64
S MA RT SC AN
®
mains supply
boosted by a pump.
pump. No need for water tank
due to low pump flow.
6.8.4 Mains Water
Supplies
Flow requirement of
64m2 plus 25lpm
(domestic) or 50lpm
(residential)
Descriptive
Priority valve not expected to be
required. Maximum of 12lpm (for
64m2 coverage if 2 pumps are
connected to run in same room)
plus 25lpm (or 50lpm) should be
easily achievable due to low pump
flow. Install to be validated as
part of commissioning procedure.
Complies with
requirement.
6.9 Backflow
Prevention
Descriptive
WRAS approved backflow check
valve included in every install
Complies with
requirement.
6.10 Nozzle
coverage and
location
Spacing, positioning,
height
Descriptive
Automist's different principle of
operation requires different
locations as per Technical
Handbook which must be
followed. (typical for pre-
engineered systems).
Alternative coverage and
positioning permits
proven performance by
testing. Compliance with
prescriptive requirements
is not necessary for
performance.
6.11 Components
testing and
certification
Performance
There is no LPCB nozzle
certification available yet but
Automist has been internally
tested against UL 2167.
Meets performance
requirements through in-
house testing.
6.11.2.3 Pipes and
Fittings
Descriptive
Automist accepts the use of
stainless steel piping, as per
standard or flexible hoses as per
Plumis spec.
Complies with
requirement.
6.11.3.5 Valves
Descriptive
a) labelled stop valve is present
upstream of pump
b) system test valve not required
as open nozzle (system flow and
integrity tested at nozzle)
c) drain valve not required as
open nozzle (quick disconnect
used for water purge)
Complies with the
requirements which are
applicable.