Example: At Front of Built-in Cupboard
Where a spray head is in line with the front of a built-in cupboard, access to the cupboard prevents
obstruction.
Figure 7: In line with front of built-in cupboard. The distance of 3.8m to the end of the cupboard is greater than
3m and therefore the spray can be assumed unobstructed in this direction. The proximity to a wall ensures that
there is no potential for meaningful obstruction in the other direction. Thus this is a Preferred Position.
Example: Adjacent to an Opening
A spray head placed next to an opening guarantees that unknown obstructions will not be placed
obstructing the spray pattern.
Figure 8: Preferred Position for spray head near openings. The head is assumed unobstructed between the kitchen
units and the right-hand end of the sliding doors. If distance d is greater than 3m then the spray pattern is
assumed unobstructed by potential obstructions to our right. See Figure 11 for example treatment of a kitchen
worktop.