Specifying Automist
Automist design specification guidelines state that a single pump can cover an area of up to 32m
2
, with a
maximum ceiling height of 3.5m. Based on third party test data, spray heads must be located within 5m line
of sight of any possible fire location.
Small potentially blocked or shadowed floor areas shall be permitted on a horizontal plane in
compartments of 64 m
2
(two pump units) or less as long as the maximum area of the total contiguous
shadowed floor area, regardless of geometric configuration, does not exceed 2 m
2
.