Automist
®
Fixed Wall Head Handbook v1.2.3
Plumis Ltd Copyright © 2017. All Rights Reserved.
Page 41 of 41
S MA RT SC AN
®
Servicing Fixed Automist System
1.
Make sure the height of the head is between 1400-1500mm and is not been obstructed.
2.
First open the nozzles and check for any blockages
3.
Check at the back of the head and make sure that PTFE is between the head and the straight
connector.
4.
Check that the 90-degree bend has been used and hoses are not kinked.
5.
Visually (when possible) check the high pressure hose for damages or tears have developed.
6.
Make sure the house coding or the wiring of the Heat Detector is correct
7.
Make sure the power cable and the breaker is sufficient for the number of pumps and head
detectors (if the head detectors are hard wired).
8.
If the nozzles are blocked clean them (or replace them) and commission the system without the
nozzles so the high pressure hoses can be flushed of any debris.
9.
Insert the nozzles and commission the system
10.
Check the pressure/ Record the new pressure (75-100 bar)
11.
Check for leaks.