0507347110/160114/B SHIELD fire safety solutions (5k1)

| INSTALLATION | EN - 13

8.1

Product description and operation

Detector for smoke detection, based on light scattering by air 
sampling tube. The sampling tube transports the air to the 
smoke detector. When smoke is detected for more than 30 
seconds

1

, it triggers an alarm. The smoke detector is fitted with 

the following features:

Fig. 8.1
A Opening for test spray
B Sensor LED (2);

- LED is off: sensor is OK
- LED is on: sensor must be replaced

C Service indicator: status LEDs that indicate the sensor 

contamination;
- green LED is on: sensor is OK
- yellow LED is flashing: sensor is 75% contaminated
- red LED is on: sensor is 100% contaminated

Fig. 8.1

8.2

Installation 

The smoke detector is available with two different air sampling 
tube lengths, that are suitable for different duct diameters; 

Location:

- on filter outlet duct (airflow >1 m/s)
- min. 3x duct diameter before a change in duct direction or 

damper; min. 5x duct diameter after these devices

- before or after the sliding valve, whatever is practical
- any position on the duct (top/bottom/front/back)
in line with the airflow direction; refer to Fig. 8.4.

It is recommended to mount the smoke detector on the front 
side of the duct in view of the visibility of the status LEDs. In 
case the LEDs are not (clearly) visible, an external light tower 
must be installed as additional warning device to indicate the 
sensor contamination.

To mount the smoke detector, proceed as follows. 

Drill a hole Ø 51 mm (2 in.) in the duct at the intended 
mounting position. 

Determine the correct tube length according to the table 
below. 

Fig. 8.2

Remove the end cap (A).

Shorten the length of the air sampling tube at the side of the 
removed end cap; 
- do 

not

 cut the other side of the tube. 

Reinsert the end cap.

Fig. 8.2

 

Fig. 8.3

Put the air sampling tube (C) in the connection tube (B). 

Insert the connection tube in the housing of the smoke 
detector.

Secure the tubes with the locking screw (A). 

8

SMOKE DETECTOR

Scope of supply:

- smoke detector 
- air sampling tube
- connection tube
- rubber bushing (T600: 1 

pc, T1500: 2 pcs)

- mounting bracket
- test spray 250 ml
- cable gland
- locknut
- self-tapping screws

1.

Alarm delay time of 30 seconds

The smoke detector enters into alarm when it has detected smoke for 

more than 30 seconds continuously. This feature prevents the smoke 

detector to be activated unintentionally by fluctuations in filter 

efficiency, which makes it pre-eminently suitable for use in filter 

systems.

A

B

C

ATTENTION

Particularly in case of a new installation, the inside of 
the duct can be polluted, e.g. by remainders of duct 
mounting material. Before installation of the smoke 
sensor, the duct must be flushed to avoid   unnecessary 
pollution of the smoke sensor. 

Penetration of air sampling 

tube through duct

± 90%

100%

Ø 250 mm

Ø 10 in.

± 325 mm

± 13 in.

Ø 315 mm

Ø 12 in.

± 385 mm

± 15 in.

Ø 400 mm

Ø 16 in.

± 460 mm

± 18 in.

Ø 500 mm

Ø 20 in.

± 550 mm

± 22 in.

Ø 630 mm

Ø 25 in.

± 750 mm

± 29.5 in.

Ø 700 mm

Ø 28 in.

± 820 mm

± 32.5 in.

ATTENTION

To prevent the smoke detector from malfunctioning, 
the end cap must always be installed.

A

x

Summary of Contents for Shield 5k1

Page 1: ...www plymovent com EN Fire safety solutions EN Installation and user manual shield 5k1...

Page 2: ...general convenience of our clients It has been based on general data pertaining to construction material properties and working methods known to us at the time of issue of the document and is therefo...

Page 3: ...B ranging from MDB 4 to MDB 48 other sizes on request central fan type SIF system control panel SCP round ductwork of the appropriate diameter 1 3 Functional description of SHIELD fire safety solution...

Page 4: ...after activation thus preventing re ignition The amount of aerosol is proportional to the filter volume and can be easily adapted by adding generators The system control panel SCP M controls the filte...

Page 5: ...cifications given in this installation manual must not be altered Modifications Modification of parts of the product is not allowed Product combinations Since the products are used in combination with...

Page 6: ...es off fan motor is switched off release of compressed air through solenoid valve After a delay of 5 seconds sliding valves close release of aerosol by FlameShield generators during 60 seconds After a...

Page 7: ...nect the FlameShield module s Make sure the panel is in RUN mode 5 1 Product description and operation ShieldControl 5k1 is a fire detection panel1 with a separate manual call point It has three detec...

Page 8: ...the mains in accordance with the electrical diagram on page 29 5 5 Maintenance The ShieldControl panel itself does not require specific maintenance except for cleaning Do not use solvents or detergent...

Page 9: ...10 160114 B SHIELD fire safety solutions 5k1 INSTALLATION EN 8 Fig 5 1 5 6 4 Reset Refer to paragraph 17 2 1 on page 24 for the reset procedure NC NO field wiring toggle switch white red terminal stri...

Page 10: ...sets of temperature detectors must be wired in parallel The detectors act as one sensor and are connected to Zone 2 ref electrical diagram on page 29 End of line resistor REOL The last detector that...

Page 11: ...status ShieldControl should indicate a fire in Zone 2 To perform the test proceed as follows Observe the functional testing instructions as described in paragraph 4 4 Functionally test all heat detect...

Page 12: ...t of the tool Push the flange completely through the hole in the duct and insert the split washer by rotating it into the inside of the duct Gently pull the flange back through the hole with the inser...

Page 13: ...having local jurisdiction Cleaning intervals differ per situation and regular checks need to be performed to set the cleaning interval for your specific situation To clean and test the spark detectors...

Page 14: ...mount the smoke detector proceed as follows Drill a hole 51 mm 2 in in the duct at the intended mounting position Determine the correct tube length according to the table below Fig 8 2 Remove the end...

Page 15: ...the supplied self tapping screws The arrow on the mounting bracket must correspond with the airflow direction through the duct Fig 8 4 Post installation checks Check that all screws are tightened Che...

Page 16: ...LEDs extinguishes at the same time Place the cap back on the test opening 8 5 Maintenance The sensor wil become polluted over time When the sensor is 75 contaminated it must be replaced This is indic...

Page 17: ...ed locally connection wire 5 x 20 AWG cable Wiring Connect the sliding valves to the system control panel SCP in accordance with the electrical diagram on page 29 Connect the reed contacts to the syst...

Page 18: ...er the fire alarm Post installation checks Check electrical connections Check pneumatic connections Check bolts and nuts for correct tightening 9 5 Functional test The sliding valves can be tested man...

Page 19: ...main compressed air line between pressure reducer and filter unit It is recommended to mount the valve on the filter housing Mount the solenoid valve at an appropriate position 10 3 Electrical connect...

Page 20: ...lation position of FlameShield must be as follows Fig 11 1 A Filter cartridge B Junction box C Framework MDB D Mounting bracket FlameShield E FlameShield module Fig 11 1 To install the FlameShield mod...

Page 21: ...A true functional check can be done by replacing the FlameShield module with the detonation simulator supplied and create a fire condition e g by removing one of the spark detectors After fire alarm t...

Page 22: ...in RUN mode 6 Test the detectors and system control panel SCP as instructed to make sure that the system is reacting as expected and required 7 Reset the panel detectors and system control panel SCP...

Page 23: ...functionally tested through exposure to daylight and the signal being monitored by ShieldControl Check OK 1 Is the smoke detector placed in the filter outlet duct 2 Is the mounting bracket correctly i...

Page 24: ...sed 3 Is the solenoid functionally tested after a fire test alarm in the complete system set up Check OK 1 Are FlameShield modules undamaged 2 Is the correct number of FlameShield modules being instal...

Page 25: ...s Reset alarm condition Determine cause e g fire and only push SYSTEM RESET after cause has been settled Panel will go to normal and display will show SYSTEM OK Program switch in RUN This action will...

Page 26: ...maintenance procedure on spark detectors ref paragraph 7 5 Follow maintenance procedure on smoke detector ref paragraph 8 5 Disconnect the ShieldControl panel Replace the FlameShield module s Perform...

Page 27: ...d After the life of the product dispose it of in accordance with federal state or local regulations activated FlameShield generators can be disposed of as non hazardous waste non activated FlameShield...

Page 28: ...in a particular environment and to perform a specific task The entire installation must comply with the relevant directives and standards The assembly instructions given by the manufacturer as well as...

Page 29: ...MDB 8 V MDB 8 H MDB 10 1x FS 200 1x FS 200 1x FS 500 1x FS 500 1x FS 500 MDB 4 MDB 12 MDB 12 V MDB 12 H MDB 16 MDB 16 H MDB 16 V 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 1x FS 500 MDB 20 MDB...

Page 30: ...SHIELD fire safety solutions 5k1 ELECTRICAL DIAGRAM 29 Electrical diagram 900010G0026 0 22 05 2014...

Page 31: ......

Page 32: ...www plymovent com 0507347110 160114 B SHIELD 5k1 EN...

Reviews: