Inputs/outputs
Digital inputs:
hide
Display suppression (with
hide
= 1 the page is not displayed in the operation.
lock
Adjustment locking (with
lock
= 1 the values are not adjustable by means of keys
ID
).
d1
...
d6
Process statuses to be displayed. (Default = 0)
store
With a positive flank (0
r
1) the input values are used as output values.
Digital outputs:
z1
...
z6
Valid process values
Analog inputs:
x1
...
x6
Process values to be displayed (default = 0)
Analog outputs:
y1
...
y6
Valid process values
Parameter and configuration data
Parameter
Description
Range
Default
z1
...
z6
Start values for digital outputs 1...6 at power-on
0 / 1
0
Y1
...
Y6
Start values for the analog outputs 1...6 at power on
-29999...999 999
0
Configuration Description
Values
Default
Disp1
...
Disp6
Function
of display
line 1...6
display line, value ajustable
adjustable
only display line
display
t
line = empty line
empty
Mode1
...
Mode6
Type of
display
line 1...6
display line analog
analog
t
display line digital
digital
Dp1
...
Dp6
Digits behind decimal point in analog line 1...6
0 ... 3
0
Entry and display of texts
Changing the texts displayed in the unit is only possible in the engineering tool! Max. 16 characters can be entered into
each text parameter. Depending of whether a line was configured as analog or digital line, all characters (
Mode x
=
digital
) or only the first 6 characters (
Mode x
=
analog
) are displayed in the instrument.
The following values or texts are displayed in the lines:
Ü
Block number 3 digits
*
Fixed text or spaces (no access)
Ö
Title (16 digits)
ä
Parameter name (the first 6 characters of
‘Text1 a ... Text6 a’ dependent of line)
#
Value x1 ... x6 dependent of line
<
Unit (the first 6 characters of
‘Text1 b ... Text6 b’ dependent of line)
>
User texts (16 characters)
signal = 0: dependent of line of ‘Text1 a ... Text6 a’
signal = 1: dependent of line of ‘Text1 b ... Text6 b’
VWERT operating page
VWERT has an operating page, which can be selected in the operating page
menu with input ‘
hide
‘ not used.
To change the value of an input field, this value must be marked by means of
ID
(inverse display). If the value is acknowledged with
M
, it starts blink-
ing and can be adjusted with
ID
. When the required value is reached, it
must be acknowledged with
M
. If a line is configured as display, the value
of this line cannot be changed.
Visualization
9499 040 50611
VWERT ( display / definition of process values )
106
:
Ü
*
Ö
Header
=
ä
#
<
*
*
Analog line
>
*
Digital line
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...