26
Outputs
26.1
OUT1 and OUT2 ( process outputs 1 and 2 )
Functions OUT1 and OUT2 are used for process output OUT1 and OUT2 configuration and parameter setting. Dependent
of hardware, the outputs can be analog or relay outputs. Function OUT1 is firmly allocated to block number 81, function
OUT2 is firmly allocated to block number 82. They are calculated invariably in each time slot.
With digital input
d1
used as signal source, it is switched to the digital output as specified in
Mode
on an instru-
ment with relay output. With continuous output, switch-over is between 0 and 20 mA as with a logic output.
Analog input
x1
used as signal source is taken to the continuous output linearly between
x0
and
x100
dependent
of configuration. With switching output (relay or logic), switching from
x0
to
x100
is from 50% (hysteresis = 1%).
Inputs / outputs
Digital input:
d1
Input signal with digital signal conversion
Analog input:
x1
Input signal with analog signal conversion
Configuration parameters:
Parameter
Description
Values
Default
Src
Signal source
Digital input
d1
Digital
t
Analog input
x1
Analog
Mode
Signal source action
direct/normally open
direct
t
inverse/normally closed
inverse
Type
Function of the continuous output
logic 0/20 mA
logic
0...20mA
0...20mA
t
4...20mA
4...20mA
x0
Analog input value
x1
at 0%
-29 999 ... 999 999
0
x100
Analog input value
x1
at 100%
-29 999 ... 999 999
100
9499 040 50611
Outputs
215
OUT1 and OUT2 ( process outputs 1 and 2 )
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...