6. UPS installation
6.1. Disassemble and inspect
Ø
When open up packages, and take out UPS, check if it has any damage during transportation
Ø
At the same time, make sure all the switches are cut off, UPS inside should include: warranty card, instruction,
installation manual, RS232 CD-ROM, RS232 cable
6.2. UPS positioning
6.2.1. Environmental requirements of installation
Ø
Temperature: 0
℃
~+40
℃
Ø
Relative humidity: 30%~90%
Ø
Height: less than 1000 M, if height exceeds 1000M, reduce 10% usage per 1000M
Ø
The size of installation environment should be larger at least 800 mm than the front and back, left and right size
of equipment in order to convenient thermal dispersion and routine maintenance; floor force requirement: 1500
KG/M
2
.
Ensure installation has following indoor environment.
Ø
No dust
Ø
A proper indoor temperature: UPS can operate under 0~40
indoor environment, but to open it, it needs
℃
temperature to be higher than 0
℃
, the ideal temperature is 25
.
℃
Ø
Have a good cooling system, there are some feasible methods as followings:
A. Natural ventilation system: only apply to low heat and broad space.
B. Artificial ventilation system: when temperature of machine shell (TA) higher than exterior temperature (TE),
then it is necessary to install an air condition. When these two temperatures are close, the capacity of ventilation
system needs to be increased relatively.
UPS is forbidden to locate at any of following conditions
Avoid direct sunlight Avoid raining and humidity Far from fire and high temperature
Avoid rot-gas