41
*
Battery low voltage
*
Inverter failure
Wrong phase
sequence
Rectifier
switch
Input phase
sequence
Input display
date
Restart function recover
1. Checking the O/P current, overload and short circuit
2. Turn on the rectifier witch
Cut off
1. Input phase sequence not correct
2. Input lack phase
3. Replace phase sequence
Abnormal
1. Checking whether the sampling single connection
reliable. Also checking the insulation
2. Checking the adjusting whether the varistor
excursion
3. Checking whether the connector of insert
components on the circuit reliable
Abnormal
Turn on
Normal
Normal
Battery low voltage
The wires connection in
good
condition
Battery
Charger
Restart function recover
1. Cut off battery, fasten all fasteners
2. Turn on the battery switch
Cut off
1. Battery damage or leakage
2. Battery failure or low capacity
3. Replacement battery
Abnormal
1. Frequently AC failure, battery not completely charge
2. Battery capacity not setting right, charge current not
right
3. Charger failure, battery not charge
Abnormal
Turn on
Normal
Normal