8.2
Thawing
Pressing this area enables selection of a thawing cycle, managed according to the load of product to be thawed, in
compliance with the maximum quantity stated by the manufacturer.
Where possible, a slow-cooking phase or a slow c holding phase can be combined with thawing.
To make it easy, the quantity of product to be selected is divided into three load bands for each of which the controller
will load three different sets of parameters, according to the following framework.
Load band
Initial cabinet set point
Final cabinet set point
Cycle duration
Lightly loaded
r25
r28
r32
Partly loaded
r26
r29
r33
Full loaded
r27
r30
r34
These three parameters will be used to control the working cabinet set points and the duration of the thawing cycle,
equally divided into five phases following on from each other as shown.
-
Phase 1 working set point = initial set point
-
Phase 2 working set point = phase 1 set point - [(initial set point – final set point) / 4]
-
Phase 3 working set point = phase 2 set point - [(initial set point – final set point) / 4]
-
Phase 4 working set point = phase 3 set point - [(initial set point – final set point) / 4]
-
Phase 5 working set point = final set point