EVCO S.p.A.
Vcolor 869
| Installer manual ver. 1.0 | Code 144VC869E104
page 69 of 92
r20
-20
-50
99
°C/°F
(1)
Product temperature set point for the first phase of sanitation
and cabinet temperature set point for the second phase of
sanitation.
r21
24
0
24
h
Duration of second sanitation phase.
r22
-20
-50
99
°C/°F
(1)
Cabinet temperature set point for the third phase of sanitation.
r23
5
1
99
h
Maximum duration of the first sanitation phase.
r24
10
1
400
min
Duration of ice cream hardening cycle.
r25
25
-50
99
°C/°F
(1)
Initial cabinet temperature set point for light-load thawing.
r26
30
-50
99
°C/°F
(1)
Initial cabinet temperature set point for medium-load thawing.
r27
35
-50
99
°C/°F
(1)
Initial cabinet temperature set point for heavy-load thawing.
r28
10
-50
99
°C/°F
(1)
Final cabinet temperature set point for light-load thawing.
r29
12
-50
99
°C/°F
(1)
Final cabinet temperature set point for medium-load thawing.
r30
15
-50
99
°C/°F
(1)
Final cabinet temperature set point for heavy-load thawing.
r31
3
-50
99
°C/°F
(1)
Cabinet temperature set point for post-thawing conservation.
r32
240
1
999
min
Light-load thawing duration.
r33
480
1
999
min
Medium-load thawing duration.
r34
720
1
999
min
Heavy-load thawing duration.
r35
-15
-50
99
°C/°F
(1)
Cabinet temperature set point for customized blast chilling.
r36
10
-50
99
°C/°F
(1)
Product temperature set point for customized blast chilling.
r37
240
1
999
min
Duration of time controlled customized blast chilling.
r38
5
-50
99
°C/°F
(1)
Cabinet temperature set point for conservation after customized
blast chilling.
r39
80
-50
99
°C/°F
(1)
Maximum cabinet temperature set-point that can be set
PAR.
DEFAULT
MIN.
MAX.
U.M.
COOLING REGULATOR
(parameters only valid if E12=2 or 3)
rC0
2
1
15
°C/°F
(1)
Parameter rC3 differential.
rC3
5
-50
99
°C/°F
(1)
Cabinet temperature set point for blast chilling phase (for
proofing cycle).
rC4
1
0
10
°C/°F
(1)
Neutral zone relative threshold (cooling) for all proofing phases.
rC5
5
-50
++
°C/°F
(1)
Cabinet temperature set point for conservation phase in the
retarding proofing cycle
PAR.
DEFAULT
MIN.
MAX.
U.M.
HEATING REGULATOR
(parameters only valid if E12=2 or 3)
rH0
2
1
15
°C/°F
(1)
Parameter rH3, rH4, rH5, rH10 and rH13 differential.
rH3
20
-50
99
°C/°F
(1)
Cabinet temperature set point for re-awakening phase.