EVCO S.p.A.
Vcolor 869
| Installer manual ver. 1.0 | Code 144VC869E104
page 71 of 92
rU8
80
0
100
%
Pre-set % humidifying during proofing
rU9
80
0
100
%
Pre-set % humidifying during holding
rU10
80
0
100
%
Pre-set % humidifying during slow cooking.
rU11
80
0
100
%
Pre-set % humidifying during holding after slow cooking.
PAR.
DEFAULT
MIN.
MAX.
U.M.
COMPRESSOR PROTECTION
C0
0
0
240
min
Minimum time between restoration of power supply after a
power failure happening during an operating cycle and
compressor switch-on.
C2
3
0
240
min
Minimum time between compressor switch-off and subsequent
switch-on.
C3
0
0
240
min
Minimum compressor-on time.
C4
10
0
240
min
Compressor-off time during cabinet probe error (“
CABINET
PROBE”
code) happening during conservation after blast
chilling and blast-freezing. See also parameters C5 and C9
C5
10
0
240
min
Compressor-on time during cabinet probe error (“
CABINET
PROBE”
code) happening during conservation after blast
chilling. See also parameter C4.
C6
80
0
199
°C/°F
(1)
Condenser temperature above which the condenser overheating
alarm is activated (“
COND OVERHEAT
” code).
C7
90
0
199
°C/°F
(1)
Condenser temperature above which the compressor locked
alarm is activated (“
COMP LOCKED
” code), once the time set
for C8 has elapsed.
C8
1
0
15
min
Activation delay of the compressor locked alarm (“
COMP
LOCKED
” code) due to threshold C7 exceeded.
C9
30
0
240
min
Compressor-on time during cabinet probe error (“
CABINET
PROBE
” code) happening during conservation after blast-
freezing. See also parameter C4
C10
5
1
240
s
Compressor switch-on delay (if at least one relay is configured
as compressor 2)
PAR.
DEFAULT
MIN.
MAX.
U.M.
DEFROSTING
d0
8
0
99
h
Defrost interval
0 = defrost at intervals is never activated.
d1
1
0
4
- - - -
Type of defrost
0 = electrical (during defrosting the compressor is switched
off, the defrost output is activated and the evaporator
fan switched off).
1 = hot gas (during defrosting the compressor is switched
on, the defrost output is activated and the evaporator
fan is switched off).
2 = air (during defrosting the compressor is switched off and
the defrost output is activated. The evaporator fan is
switched on, regardless of the door status, or regardless
of the status of the door switch input)
3 = air with the door open (during defrosting the compressor
is switched off and the defrost output is activated. The
evaporator fan is switched on, provided the door is open
or provided the door switch input is on and that