EVCO S.p.A.
Vcolor 869
| Installer manual ver. 1.0 | Code 144VC869E104
page 72 of 92
parameter i0 is set to a value other than 0).
d2
2
-50
99
°C/°F
(1)
Evaporator temperature to end defrosting. See also parameter
d3
d3
30
0
99
min
If the evaporator probe is not present (P4=0), it sets the
defrost duration.
If the evaporator probe is present (P4=1), it sets the maximum
defrost duration. See also parameter d2
0 = defrost is never activated.
d4
0
0
1
- - - -
Enable defrost at the start of blast chilling and of blast-freezing
0 = no
1 = yes
d5
30
0
99
min
Defrost delay from the beginning of conservation
0 = defrost will be activated once the time set by d0 has
elapsed.
d7
2
0
15
min
Drip time after a defrost, in which the compressor and the
evaporator fan are switched off and the defrost output is
deactivated.
d15
0
0
99
min
Minimum consecutive compressor-on duration for starting hot
gas defrost, if d1 is set to 1
d16
0
0
99
min
Pre-drip time if d1 is set to 1 (hot gas defrost), in which the
compressor and the evaporator fan are off and the defrost
output remains activate.
PAR.
DEFAULT
MIN.
MAX.
U.M.
TEMPERATURE ALARMS
A1
10
0
99
°C/°F
(1)
Cabinet temperature below which the minimum temperature
alarm is activated (in relation to the working set point, i.e.
“r10–A1” during conservation after blast chilling and “r11–A1”
during
conservation
after
blast-freezing;
(“
LOW
TEMPERATURE
” code). See also parameter A11
A2
1
0
1
- - - -
Enable minimum temperature alarm (“
LOW TEMPERATURE
”
code):
0 = no
1 = yes
A4
10
0
99
°C/°F
(1)
Cabinet temperature above which the maximum temperature
alarm is activated (relating to the working set point, i.e.
“r10+A4” during conservation after blast chilling and “r11+A4”
during
conservation
after
blast-freezing
(“
HIGH
TEMPERATURE
” code). See also parameter A11 (4)
A5
1
0
1
- - - -
Enable maximum temperature alarm (“
HIGH TEMPERATURE
”
code):
0
=
no
1
=
yes
A7
15
0
240
min
Temperature alarm delay (“
HIGH TEMPERATURE
” code and
“
LOW TEMPERATURE
” code)
A8
15
0
240
min
Maximum temperature alarm delay (“
HIGH TEMPERATURE
”
code) from the end of the evaporator fan-off time and from the
beginning of conservation.