EVCO S.p.A.
Vcolor 869
| Installer manual ver. 1.0 | Code 144VC869E104
page 75 of 92
PAR.
DEFAULT
MIN.
MAX.
U.M.
DIGITAL INPUTS
i0
2
0
2
- - - -
Effect caused by the door opening, or when the door switch
input is activated.
0 = no effect and no signal
1 = the compressor, evaporator fan, thawing heater, heater
and humidifier are switched off and the cabinet light is
on, once the time set by parameter i2 has elapsed, the
device displays the alarm and the buzzer is activated
until the door is closed. See also parameter F15
2 = the evaporator fan is switched off and the cabinet light is
on, once the time set by parameter i2 has elapsed, the
device displays the alarm and the buzzer is activated
until the door is closed. See also parameter F15.
i1
0
0
1
- - - -
Door switch input polarity
0 = normally open (input active with contact closed)
1 = normally closed (input active with contact open)
i2
5
-1
120
min
Door-open time for door-open alarm record;
-1 =
alarm not signalled.
i5
-
-
-
- - - -
unused
i6
0
0
1
- - - -
High pressure input polarity
0 = normally open (input active with contact closed)
1 = normally closed (input active with contact open)
i7
5
-1
240
s
High-pressure alarm signal delay
-1 = alarm not signalled
i8
-
-
-
- - - -
unused
i9
0
0
1
- - - -
Low pressure input polarity
0
=
normally open (input active with contact closed)
1
=
normally closed (input active with contact open)
i10
5
-1
240
s
Low-pressure alarm signal delay
-1 = alarm not signalled
i11
0
0
1
- - - -
Thermal switch input polarity
0 = normally open (input active with contact closed)
1 = normally closed (input active with contact open)
i12
5
-1
240
s
Thermal switch alarm signal delay
-1 =
alarm not signalled
i13
-
-
-
- - - -
unused
PAR.
DEFAULT
MIN.
MAX.
U.M.
DIGITAL OUTPUTS