EVCO S.p.A.
Vcolor 869
| Installer manual ver. 1.0 | Code 144VC869E104
page 79 of 92
16
ALARMS
16.1
Alarms
The table below lists the various alarms.
Code
Meaning
RTC
Clock error.
To correct
-
Re-set the date and time.
Main consequences
-
The device will not memorise the date and time an HACCP alarm happened.
-
The alarm output will be activated.
CABINET PROBE
Cabinet probe error.
To correct
-
Check the parameter P0 value.
-
Check that the probe is undamaged.
-
Check the device-probe connection.
-
Check the cabinet temperature.
Main consequences
-
If the error happens during stand-by, it will not be possible to set or start any
operating cycle.
-
If the error happens during blast chilling or blast-freezing, the cycle will continue with
the compressor in continuous mode.
-
If the error happens during conservation, the compressor will operate according to
parameters C4 and C5 or C9.
-
If the error happens during a proofing, slow cooking or a thawing cycle, the cycle will
be interrupted.
-
The minimum temperature alarm will never be activated.
-
The maximum temperature alarm will never be activated.
-
The door heaters will never be switched on.
-
The alarm output will be activated.
EVAPORATOR
PROBE
Evaporator probe error.
To correct:
-
The same as for the cabinet probe error but with reference to the evaporator probe.
Main consequences
-
If parameter P4 is set to 1, defrosting will last for the time set by parameter d3.
-
Parameter F1 will have no effect.
-
The alarm output will be activated.