EVCO S.p.A.
Vcolor 869
| Installer manual ver. 1.0 | Code 144VC869E104
page 80 of 92
CONDENSER
PROBE
Condenser probe error.
To correct
-
The same as for the cabinet probe error but with reference to the condenser probe.
Main consequences
-
The condenser fan will operate in parallel with the compressor.
-
The condenser overheat alarm will never be activated.
-
The compressor locked alarm will never be activated.
-
The alarm output will be activated.
NEEDLE PROBE
SENSOR 1
Needle probe/sensor 1 error.
To correct
-
The same as for the cabinet probe error but with reference to needle probe 1.
Main consequences if parameter P3 is set to 1 (single probe)
-
If the error happens during stand-by, the temperature controlled cycles will be started
up as time-controlled.
-
If the error happens during temperature controlled blast chilling, blast chilling will last
for the time set by parameter r1
-
If the error happens during temperature controlled blast-freezing, blast-freezing will
last for the time set by parameter r2
-
If the error happens during needle probe heating, the heating will be interrupted.
-
The alarm output will be activated.
Main consequences if parameter P3 is set to 2 or 3 (multineedle or multi-sensor probes)
-
The device will not use the probe/sensor showing the error but the other available
probes or sensors will be used.
NEEDLE PROBE
SENSOR 2
Needle probe/sensor 2 error.
To correct
- The same as for the cabinet probe error but with reference to needle probe 2.
Main consequences
-
The device will not use needle probe 2.
NEEDLE PROBE
SENSOR 3
Needle probe/sensor 3 error.
To correct
- The same as for the cabinet probe error but with reference to needle probe 3.
Main consequences
-
The device will not use needle probe 3.
THERMAL
SWITCH
Thermal switch alarm
To correct
-
Check the state of the thermal switch input.
-
Check the value of parameter i11.
Main consequences
-
The cycle in progress will be interrupted
-
The alarm output will be activated.