POLITEC s.r.l. | Manuale MANA IR SMA – Ver. 2.5
24
9.
CALIBRATION THROUGH SMA SYSTEM
1)
Start the alignment of the transmitter is on the barrier by checking the position of the DIP switch 7 to ON
and activating the TEST optics TX (1 or 2 or 3 or 4), by pressing the dedicated button for about 3 seconds
until the orange LED TEST will lit up.
2)
Place in the corresponding optical TEST (1 or 2 or 3 or 4) on coral receiver, checking the position of the
DIP switch 7 to ON and pressing the dedicated button for 3 seconds until the the BUZZER and the LED
TEST turns ON, (with high brightness)
3)
Place the filter in front of the optic Transmitter you are aligning.
It is recommended that the calibration with the use of the filter over long distances and
then search for the maximum signal.
TEST
BUTTON
DIP 7 ON
ORANGE
LED
DIP 7 ON
TO ACTIVATE
THE LED
DIP 7 ON
TO ACTIVATE
THE LED
TEST
BUTTON
DIP 7 ON
ORANGE
LED