POLON 4000

 

INTERACTIVE FIRE DETECTION AND ALARM SYSTEM 

 

EKS-4001 

MICROPROCESSOR-BASED 

ADDRESSABLE MONITORING  

AND CONTROLLING ELEMENT 

 

Installation and Maintenance Manual 

IK-E286-001E 

 

IIIB Edition 

Summary of Contents for EKS-4001

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM EKS 4001 MICROPROCESSOR BASED ADDRESSABLE MONITORING AND CONTROLLING ELEMENT Installation and Maintenance Manual IK E286 001E IIIB Edition ...

Page 2: ...polon alfa pl web site 1438 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 06 1438 CPD 0071 EN 54 18 Input output device EKS 4001 addressable monitoring and controlling element Technical data IK E286 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the man...

Page 3: ...olled device by line continuity monitoring circuit 615 µA Relay controlling output non potential switchable contact 2 A 30 V Tp relay actuation delay time 2 s 30 s 60 s 90 s Number of monitoring outputs 2 Monitoring lines capacity 65 nF ca 350 m of 1x2x0 8 mm cable Monitoring output initiation NO or NC non potential contact Tk elapsing time after which controlled device monitoring starts no monito...

Page 4: ...he module with the terminal block in the CUBO S type case The following case sizes are available for one two and four EKS 4001 modules The case bases are drilled in the corners to provide openings for wall mounting Two PG7 cable gland seals are located in the case base side wall in order to insert the detection line inputs and outputs Additionally two or four depending on the case type PG9 cable g...

Page 5: ...e control panel information about a non maskable fault The way how the monitoring and controlling element works is determined by the element operation mode During the system automatic configuration the default mode settled by the manufacturer is set i e 10000000 in the binary recording 80 in the hexadecimal recording It means that the EKS monitors the controlled device line continuity the relay ac...

Page 6: ...land seals are properly sealed and unused gland seals are plugged all cable gland seals are plugged by default For installation wires connection a screw driver use is recommended its operation part should be pushed in as far as it goes see below figure into the connector smaller hole Then the wire should be inserted into the bigger hole and the screw driver should be taken off It is advised to use...

Page 7: ...ld not be exposed to either direct sunlight or heat from heating equipment The EKS 4001 elements storage period in transportation packing should not exceed 6 months The EKS 4001 monitoring and controlling elements should be carried in closed transport means spaces in packing that meets the requirements of transportation regulations in force The temperature during transportation should not be lower...

Page 8: ...8 IK E286 001E Fig 2 1xEKS case dimensions ...

Page 9: ...IK E286 001E 9 Fig 3 2xEKS case dimensions ...

Page 10: ...10 IK E286 001E Fig 4 4xEKS case dimensions ...

Page 11: ...IK E286 001E 11 Fig 5 Exemplary diagram of EKS 4001 element in 1xEKS case connection in detection line Fig 6 EKS case connection terminals view IK E286 001 03 2009 05 2012 ...