PURPOSE 

The EKS-4001 monitoring and controlling element is an addressable device designed: 

-

 

to control automatic protection and fire-fighting devices, 

-

 

to monitor the above mentioned devices actuation, 

-

 

to monitor any other equipment. 

The  EKS-4001  element  is  intended  to  operate  in  loop-shaped  detection  lines  of  the  POLON  4000 
system  control  panels  as  an  input/output  device  with  one  controlling  output  and  two  monitoring 
inputs.  The  EKS-4001  element  is  designed  for  indoor  and  outdoor  operation  in  the  ambient 
temperature range between -25 

°C and +55

 

°C, and relative humidity up to 95

 % at +40 

°C.

 

 

 

2  

TECHNICAL SPECIFICATIONS 

Operation voltage 

16.5 V ÷ 24.6 V

 

Current draw from detection line (in quiescent mode) 

< 165 µA

 

Controlled device power supply voltage 

6 V ÷ 30 V

 

Current draw from power supply unit of controlled device  
 

by line continuity monitoring circuit 

< 615 µA

 

Relay controlling output 

non-potential switchable contact 2 A/30 V 

Tp relay actuation delay time 

2 s, 30 s, 60 s, 90 s 

Number of monitoring outputs  

Monitoring lines capacity 

≤ 65 nF (

ca. 350 m of 1x2x0.8 mm cable) 

Monitoring output initiation 

NO or NC non-potential contact  

Tk elapsing time after which  
 

 controlled device monitoring starts  

no monitoring, 40 s, 70 s, 130 s 

Cable routing: 

-

 

for detection line wires 

2 x PG7 wire gland seal 

-

 

for monitoring and controlling  wires 

1 x PG9 wire gland seal 

Address coding method 

programmable from control panel 

Admissible relative humidity 

up to 95 % at 

40 °C

 

Climate category 

25/055/04 

EKS module cover plate colour 

white 

Module 

dimensions

 

acc. to Fig. 1. 

1xEKS case dimensions 

acc. to Fig. 2. 

2xEKS case dimensions 

acc. to Fig. 3. 

4xEKS case dimensions 

acc. to Fig. 4. 

EKS module mass 

60 g 

1xEKS case mass 

290 g 

2xEKS case mass 

440 g 

4xEKS case mass 

630 g 

Cases ingress protection 

IP 65 

Cases colour 

grey bottom, transparent cover plate. 

Summary of Contents for EKS-4001

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM EKS 4001 MICROPROCESSOR BASED ADDRESSABLE MONITORING AND CONTROLLING ELEMENT Installation and Maintenance Manual IK E286 001E IIIB Edition ...

Page 2: ...polon alfa pl web site 1438 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 06 1438 CPD 0071 EN 54 18 Input output device EKS 4001 addressable monitoring and controlling element Technical data IK E286 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the man...

Page 3: ...olled device by line continuity monitoring circuit 615 µA Relay controlling output non potential switchable contact 2 A 30 V Tp relay actuation delay time 2 s 30 s 60 s 90 s Number of monitoring outputs 2 Monitoring lines capacity 65 nF ca 350 m of 1x2x0 8 mm cable Monitoring output initiation NO or NC non potential contact Tk elapsing time after which controlled device monitoring starts no monito...

Page 4: ...he module with the terminal block in the CUBO S type case The following case sizes are available for one two and four EKS 4001 modules The case bases are drilled in the corners to provide openings for wall mounting Two PG7 cable gland seals are located in the case base side wall in order to insert the detection line inputs and outputs Additionally two or four depending on the case type PG9 cable g...

Page 5: ...e control panel information about a non maskable fault The way how the monitoring and controlling element works is determined by the element operation mode During the system automatic configuration the default mode settled by the manufacturer is set i e 10000000 in the binary recording 80 in the hexadecimal recording It means that the EKS monitors the controlled device line continuity the relay ac...

Page 6: ...land seals are properly sealed and unused gland seals are plugged all cable gland seals are plugged by default For installation wires connection a screw driver use is recommended its operation part should be pushed in as far as it goes see below figure into the connector smaller hole Then the wire should be inserted into the bigger hole and the screw driver should be taken off It is advised to use...

Page 7: ...ld not be exposed to either direct sunlight or heat from heating equipment The EKS 4001 elements storage period in transportation packing should not exceed 6 months The EKS 4001 monitoring and controlling elements should be carried in closed transport means spaces in packing that meets the requirements of transportation regulations in force The temperature during transportation should not be lower...

Page 8: ...8 IK E286 001E Fig 2 1xEKS case dimensions ...

Page 9: ...IK E286 001E 9 Fig 3 2xEKS case dimensions ...

Page 10: ...10 IK E286 001E Fig 4 4xEKS case dimensions ...

Page 11: ...IK E286 001E 11 Fig 5 Exemplary diagram of EKS 4001 element in 1xEKS case connection in detection line Fig 6 EKS case connection terminals view IK E286 001 03 2009 05 2012 ...

Reviews: