IK-E286-001E 

3  

SAFETY CONDITIONS  

3.1 Repairs and maintenance  

Any maintenance works or periodic inspections shall be executed by skilled personnel employed by 
companies authorised and trained by POLON-ALFA.  

Any  repairs  must  be  carried  out  by  the  manufacturer.  POLON-ALFA  bears  no  responsibility  for  the 
operation of any apparatus being repaired by unauthorised personnel. 
 

3.2 Works at height  

Any detector installation works carried out at height must be executed with particular care utilising 
tools and machinery in good working condition. Special attention shall be given to stability of ladders, 
elevators, lifts, etc. 

Any  electric  tools  shall  be  used  strictly  obeying  the  safety  rules  stated  in  instruction  manuals  by 
manufacturers.  
 

3.3 Anti-dusting eye protection 

It  is  obligatory  to  use  protective  anti-dusting  glasses  and  masks  during  the  EKS-4001  element 
installation works that produce high amount of dust, such as hole drilling in walls and ceilings. 
 
 

4  

DESIGN DESCRIPTION 

The  EKS-4001 monitoring and controlling element  (Fig. 1)  is a replaceable module  in the form of a 
printed board with electronic circuits, enclosed by a cover, placed in a case furnished with a terminal 
block.  Two illuminating diodes  are  located on the module cover outer  side, on the opposite  side 

 

two  angle  plugs  are  placed  that  enable  connection  of  the  module  with  the  terminal  block  in  the 
CUBO S type case. The following case sizes are available: for one, two and four EKS-4001 modules. 

The case bases are drilled in the corners to provide openings for wall mounting. Two PG7 cable gland 
seals are located in the case base side wall in order to insert the detection line inputs and outputs. 
Additionally,  two  or  four  (depending  on  the  case  type)  PG9  cable  gland  seals  are  provided  to 
introduce the monitoring and controlling wires. A mounting plate with two slots for modules is fixed 
to the case base. One slot is designed for connection of the detection line input and output wires; the 
other one 

 for connection of the monitoring and controlling wires. Screens of the detecting line and 

monitoring and controlling cables should be connected to the clamps located between the slots. The 
case  cover  plate  with  a  rubber  seal  is  fastened  to  the  case  base  with  four  plastic  screws.  Special 
attention should be given to proper alignment of the lug and opening located diagonally. 

 

 

5  

PRINCIPLES OF OPERATION 

Communication  between  the  POLON  4000  system  control  panel  and  the  EKS-4001  monitoring  and 
controlling  element  is  provided  by  a  two-core  addressable  detection  line.  The  monitoring  and 
controlling element is equipped with a short circuit isolator. Actuation of a fire-fighting device (e.g. a 
smoke damper) or signalling device (e.g. a buzzer or optical indicator) is achieved due to the element 
relay contacts closing evoked by a command from the control panel. The monitoring and controlling 

Summary of Contents for EKS-4001

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM EKS 4001 MICROPROCESSOR BASED ADDRESSABLE MONITORING AND CONTROLLING ELEMENT Installation and Maintenance Manual IK E286 001E IIIB Edition ...

Page 2: ...polon alfa pl web site 1438 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 06 1438 CPD 0071 EN 54 18 Input output device EKS 4001 addressable monitoring and controlling element Technical data IK E286 001 manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instructions contained in the man...

Page 3: ...olled device by line continuity monitoring circuit 615 µA Relay controlling output non potential switchable contact 2 A 30 V Tp relay actuation delay time 2 s 30 s 60 s 90 s Number of monitoring outputs 2 Monitoring lines capacity 65 nF ca 350 m of 1x2x0 8 mm cable Monitoring output initiation NO or NC non potential contact Tk elapsing time after which controlled device monitoring starts no monito...

Page 4: ...he module with the terminal block in the CUBO S type case The following case sizes are available for one two and four EKS 4001 modules The case bases are drilled in the corners to provide openings for wall mounting Two PG7 cable gland seals are located in the case base side wall in order to insert the detection line inputs and outputs Additionally two or four depending on the case type PG9 cable g...

Page 5: ...e control panel information about a non maskable fault The way how the monitoring and controlling element works is determined by the element operation mode During the system automatic configuration the default mode settled by the manufacturer is set i e 10000000 in the binary recording 80 in the hexadecimal recording It means that the EKS monitors the controlled device line continuity the relay ac...

Page 6: ...land seals are properly sealed and unused gland seals are plugged all cable gland seals are plugged by default For installation wires connection a screw driver use is recommended its operation part should be pushed in as far as it goes see below figure into the connector smaller hole Then the wire should be inserted into the bigger hole and the screw driver should be taken off It is advised to use...

Page 7: ...ld not be exposed to either direct sunlight or heat from heating equipment The EKS 4001 elements storage period in transportation packing should not exceed 6 months The EKS 4001 monitoring and controlling elements should be carried in closed transport means spaces in packing that meets the requirements of transportation regulations in force The temperature during transportation should not be lower...

Page 8: ...8 IK E286 001E Fig 2 1xEKS case dimensions ...

Page 9: ...IK E286 001E 9 Fig 3 2xEKS case dimensions ...

Page 10: ...10 IK E286 001E Fig 4 4xEKS case dimensions ...

Page 11: ...IK E286 001E 11 Fig 5 Exemplary diagram of EKS 4001 element in 1xEKS case connection in detection line Fig 6 EKS case connection terminals view IK E286 001 03 2009 05 2012 ...

Reviews: