16
IK-E283-001E
DELAYS SETTING
F.08 Enter
2nd stage alarm delays setting
Function recall –
push button short pressing
Exit –
push button longer than 1 s pressing
Time for acknowl. T1 =
0’30
– T1 - delay of 2nd stage alarm without acknowledgement
2nd stage alarm delay
T2=2’30
– T2 - delay of 2nd stage alarm with acknowledgement
Selection of T1 or T2 using
push buttons
Times being programmed with
with 5-s interval. (e.g. 2’30-
means 2 min and 30 s)
Note: T1 time for acknowledgement should be shorter than T2 time
provided for alarm verification.
EVENT MEMORY
ERASURE
F.09 Enter
Event memory erasure
Function recall –
push button short pressing
Exit –
push button longer than 1 s pressing
EVENTS ERASURE ?
– Concerns events recorded in control panel memory.
NO
– NO – by default lack of event memory erasure.
Attention! Switching to YES with
push button results in erasure of all
events recorderd in control panel non-volatile memory.
DIAGNOSTIC
FUNCTIONS F.10
Enter
Diagnostic functions (intended for factory service)
Function recall –
push button short pressing
Exit –
push button longer than 1 s pressing
Software version:
V1.0
– Information name
– Value being read out
Change of displayed information with
push buttons
ACCESS CODE CHANGE
F.11 Enter
Access code change
Function recall –
push button short pressing
Exit –
push button longer than 1 s pressing
Access code change
– Operation name
Level: 2 code: 0 0
0
– Access level No., 3-digit code
Note: Default codes restoration is done automatically – by closing 1-2
contacts of S15 jumper located on printed board – Fig. 2
DATE & TIME SETTING
F.12 Enter
Date and time setting
Function recall –
push button short pressing
Exit –
push button longer than 1 s pressing
CSP IGNIS 2040
2011-01-05 15:20:44
– Copan name
– Year - month - day hour : min : sec
Selection of value being set - with
push buttons
Setting – using
push buttons.
4.9 EVENT MEMORY
The software necessary for the event memory readout and information materials are available in
Internet on the
www.polon-alfa.pl
web site after obtaining an access code.
Hardware requirements concerning PC computer:
o
accessible USB port;
o
hard disc of ca. 25 MB free memory;
o
installed Windows 98/ME/2000/XP/Vista/7 operating system