24
IK-E283-001E
-
consecutive testing of every fire detector (e.g. using smoke and heat imitators) and manual
call points installed in every detection line , utilising a possibility to switch any line for testing;
-
visual evaluation of the fire detectors technical condition (level of dirt, corrosion, permanent
soil) and of manual call points, especially in case of their longer operation, that should be
carried out during a device testing;
-
if necessary, cleaning of the fire detectors and their replacement or regeneration;
-
checking the external signalling devices and connected protective and fire-fighting devices
under a condition that the premises user is informed and taking necessary measures to avoid
panic or any damage in the building resulting from the test execution. The external signal
receivers and a monitoring centre must be notified of a planned test;
-
battery voltage value checking on the clamps during buffering – proper voltage value
amounts to 27.1…27.6 V;
-
battery condition checking – according to the battery manufacturer recommendations.
10.3 FUSE REPLACEMENT
The control panel is equipped with three melt fuses in the following circuits:
-
battery cluster – F1 melt fuse of F630L250 type;
-
external devices power supply – F2 melt fuse of F500L250 type;
-
mains power supply – F3 melt fuse of T3,15L250 type.
The fuses are accessible after the control panel cover plate removal; their arrangement is shown in
Fig. 2.
11 PACKING, STORAGE AND TRANSPORTATION
Packaging
The control panel is placed in a unit packing, reducing free movement possibility and eliminating
damage occurrence during loading and transportation.
The following data are marked on the package:
-
the name or the trade mark of the manufacturer;
-
the name and the type of the control panel;
Moreover, the following marking is placed on the package:
“CAUTION FRAGILE”, “UPPER SIDE, DON’T TURN OVER”, “KEEP DRY” or equivalent marks according
to the PN-85/0-79252 Polish Standard.
Storage
The control panel should be stored in closed premises at a temperature b 5
o
C and + 40
o
C
and relative humidity not exceeding 80 %, free of corrosive vapours and gases. In case the control
panel is stored for a longer period, it is necessary to connect it to a power supply for at least 1 hour
and execute operation tests every 6 months.
During storage the control panel should not be exposed to heat radiation: direct sun light or heating
devices.
Transportation
The control panels should be carried in their packing by closed transport means, taking into
consideration the transport recommendations marked on the package, and protecting them against
sharp shocks and avoiding ambient temperature exceeding the – 25
o
C to + 55
o
C range.