background image

26

27

Panel layouts

Pre-installation requirements

Planning

Before installing MHP panels ensure you have planned out the 
positioning of the required panels avoiding all other services such 
as electrics, gas and water supply.

You will not need to do any specific preparation for the 
installation in a new build property as there will be no ceilings 
or floors in place.

For existing room refurbishment, you will need to take up your 
floor if fitting from above or take down the ceiling if fitting from 
below. Ensure that the area where the MHP panels are to be 
positioned is free from any debris before commencing installation.

Installation

Installation from above

To install MHP panels from above simply fit support bearers to 
each side of the joists. These support bearers should be positioned 
30mm from the top of the joist and the MHP panel is then simply 
laid on to these supports.

Installation from below

When installing MHP panels from below you will need to mark 
out the positioning of the panels to ensure you have them 
situated in the correct places for heating the room above.

Once you have checked the marked out positioning, the MHP 
panels can be slotted into place and fixed to the underside 
of the floor using 1¾” x 8 woodscrews with M6 x 30 dia washers. 
It is advisable to use 6 fixings per panel ensuring you avoid the 
moulded pipe marking on the underside of the panel and fix 
each panel securely.

IMPORTANT NOTE:

 Polystyrene can cause deterioration to cable 

insulation when it comes into direct contact with it. 
Always ensure that electrical cables are not in physical contact 
with the MHP panels using tape or a polythene strip.

Finishing

Once you have connected your system up to the manifold and 
tested it you can then finish the room by fitting the floor or ceiling 
in the normal way depending on whether you have installed MHP 
from above or below.

Testing

Where possible installations should be tested at 20°C to 
18 bar pressure. Any installations once connected to the manifold 
have a maximum test pressure of 6 bar.

Product Information

Product 

Code 

No of panels 

 

 

per pack

MHP 490mm (W) x 2.0m (L) 

MHP49020 

5

MHP 490mm (W) x 1.3m (L) 

MHP49013 

5

MHP 380mm (W) x 2.0m (L) 

MHP38020 

MHP 380mm (W) x 1.3m (L) 

MHP38013 

5

Heat Output

Maximum floor area for flow and return 20m

2

Room at 20°C 

                

Heat output per panel

Flow 

Av. floor 

MHP49020  MHP49013  MHP38020  MHGP38013 

temp (°C) 

temp (°C) 

(W) 

(W) 

(W) 

(W)

40 

25.0 

63 

42 

49 

33

45 

25.8 

75 

50 

58 

39

50 

26.6 

86 

58 

67 

45

55 

28.9 

120 

80 

93 

62

60 

30.8 

147 

99 

114 

77

Approximate coverage required:

For 70W/m

2

 room 

= 80% coverage 

For 50W/m

2

 room 

= 60% coverage

Connect up to 3 panels in series 

Maximum coverage per circuit 20m

2

1 panel layout

15mm Polypipe flow and return 

connections to manifold

15mm Polypipe flow and return 

connections to manifold

Part No: PB010
10mm 
Straight Coupling

Part No: PB010
10mm 
Straight Coupling

Part No: PB1115
15mm - 10mm
Reduced Branch Tee

Part No: PB015
15mm
Straight Coupling
+
Part No: PB1815
15mm - 10mm
Socket Reducer

Part No: PB1115
15mm - 10mm
Reduced Branch Tee
+
Part No: PB1815
15mm - 10mm
Socket Reducer

Part No: PB1115
15mm - 10mm
Reduced Branch Tee
+
Part No: PB1215
15mm - 10mm
Reduced Branch 
Spigot Tee

2 panel layout

1

1

2

3

2

3

4

4

5

5

6

6

Summary of Contents for Under Floor Heating Systems

Page 1: ...s Broomhouse Lane Edlington Doncaster DN12 1ES Tel 01709 770 000 Fax 01709 770 001 2410 London Road Mount Vernon Glasgow G32 8XZ Tel 0141 778 8822 Fax 0141 778 2703 Dromore Road Lurgan Craigavon Co Ar...

Page 2: ...revious printed copies will become out of date The latest version of our installation advice including a downloadable version of the current Technical Installation Guide can be found at our trade webs...

Page 3: ...xtensive back up service Technical representation available to discuss systems in general and particular projects www ufch com Technical Installation CD Specialist Technical Hotline on 01709 770000 En...

Page 4: ...he floor screed is required by Building Regulations Edge insulation also acts as an expansion joint Floating Floor When installed in floating floors Polyplumb pipe is simply pressed in to the pre form...

Page 5: ...r requires a bespoke design You then simply input data for each room providing floor type room size and control zones to calculate the required pack All packs have a single order code and include all...

Page 6: ...h when heated will reduce to 8 9 and cause only a very small amount of shrinkage The floor will re absorb some moisture when the heating is not operating and the moisture content will increase to 12 1...

Page 7: ...d around the perimeter of the room using staples so as to prevent possible risk of the panels lifting Preparing the pipe Step 4 You will need to remove the coil from the bag leaving the shrink wrap on...

Page 8: ...ted the screed cover can be applied Care should be taken to ensure that the screed is tightly compacted around the pipe to ensure that no voids are present The system should remain under pressure 6 ba...

Page 9: ...nder pressure whilst the flooring is laid Finishing The room can then be finished by fitting 18mm or 22mm tongue and groove sheets of chipboard glued on the edge over the floating floor system Mark th...

Page 10: ...hed downwards and away from the underside of the timber finished floor covering as this could lead to potential underperformance of the system Testing Step 4 Once the pipe circuits have been installed...

Page 11: ...These can be fixed directly through the spreader plate down in to the joists below It is important to indicate the position of pipework in areas where the additional fixing of items such as carpet gri...

Page 12: ...heir high output at relatively low flow temperatures Modular Heating Panels are ideal for maximising heat efficiency and lowering energy consumption In most installations it is not necessary to cover...

Page 13: ...should be selected The span is defined as the free space from wall to wall that needs to remain uninterrupted by trimmers or other services Ideally install MHP panels prior to other services whenever...

Page 14: ...omes into direct contact with it Always ensure that electrical cables are not in physical contact with the MHP panels using tape or a polythene strip Finishing Once you have connected your system up t...

Page 15: ...for heavyweight floor coverings such as ceramics or where the floor covering needs to be secured directly to the panel e g solid wood Overlay Lite is a high compressive strength lightweight insulated...

Page 16: ...is should be the first consideration for most projects The more structural nature of Overlay however makes it ideal for direct tiling or application of floor finishes which need to be fixed or screwed...

Page 17: ...mple of blanking in a bathroom Example of squaring off an irregular room plan Room layouts The following diagrams show some examples of room shapes pipe requirements and interruptions pillars hearths...

Page 18: ...wood floors they can be discretely screwed through the tongue and groove directly into the Overlay panel avoiding pipe circuitry to minimise movement in the floor covering If over boarding with 6mm p...

Page 19: ...r covering as normal It is advisable to mark out pipe positioning to avoid stapling pipes when fitting carpets 36 37 Overlay Lite for lightweight floor coverings Installation Laying end returns Step 1...

Page 20: ...stic hot water primary circuits To provide independent hydraulic control of the entire system it is important that the installation is designed as an S Plan or S Plan Plus configuration which allows f...

Page 21: ...d in under floor heating systems is less than that required for radiators or stored hot water If these other services are connected to the same boiler it will be necessary to control the water tempera...

Page 22: ...iring centre and slave units Available in two surface finishes and offers the following features Large touch screen display with high visibility blue LED backlight On screen display shows current stat...

Page 23: ...distribution pipe work Connection from nearest radiator 260mm 200mm Pump Pipe thermostat Heating return Heating flow Under floor heating flow Under floor heating return Thermostatic blending valve Pu...

Page 24: ...ible tap connectors for the simplest method of connection Close all under floor heating circuits except one by screwing down the blue caps and closing the isolating valves situated on top of the manif...

Page 25: ...resistant to the build up of scale Short term chlorination for disinfection of supply pipe work and normal levels of chlorine in UK domestic water supplies will not have an adverse effect on the integ...

Page 26: ...ng should be done with all switches on and room thermostats calling Fault finding complete Adjust pump speed and set flow rates in accordance with the system design data as provided NO NO Is the boile...

Page 27: ...Manufacturing quality assurance In accordance with BS ES ISO 9001 2000 BSI registered firm Certificate FM00318 Installation standard To follow the recommendations of BS5955 Part 8 2001 Plastic Pipewo...

Page 28: ...OR HEATING REQUIREMENTS Manifold Position s Please also indicate on drawing Floor Type Solid Suspended Floating MHP Overlay Overlay Lite Ground Floor 1st Floor 2nd Floor CONSTRUCTION DETAILS If NOT to...

Reviews: